9.1 Failure signals according to NAMUR NE 107
Warnings and information messages (blue, yellow or orange LEDs) do not interrupt the
control mode!
Actuator cannot be controlled
with analogue control signal
Actuator is set to 3-point
operation or is currently
controlled by a 3-point signal
(indicated by lit LED above 3-
point connector)
By withdrawing the connector for
the 3-point signal, you can
determine whether the actuator is
set to 3-point operation or
whether it is simply being
controlled by a 3-point signal
If the LED goes out, a 3-point
signal is present, e.g. from an
anti-freezing contact
If the LED is still lit, the actuator is
set to 3-point operation. An
analogue control signal must be
present during the initialisation
run in order to control the
actuator with an analogue signal!
Repeat the initialisation with an
analogue control signal applied
Actuator oscillates continuously
about a point
Xp setting on controller is too low
Increase the Xp value (refer to
the controller Operating
Instructions)
or set the ECONOMY switch to
ON
Dead band setting on controller is
too low
Increase the dead band value
(refer to the controller Operating
Instructions)
or set the ECONOMY switch to
ON
Dirty slide
Clean surface with Greycode
(black/white)
NE 107
Colour
NAMUR description
PREMIO-Plus
Maintenance required
Blue
Urgent maintenance required
Maintenance required
Information corresponding to the
diagnostic switch:
3 = Comprises step 1 and step 2
as well as other function
checks (e.g. voltage and
frequency faults)
2 = Internal temperature exceeds
80°C for more than one hour
or oscillation detected
1 = Moisture detected inside the
actuator for more than one
hour or maximum hysteresis
band active for more than one
hour
0 = Off
Fault
Possible Causes
Remedy