beautypg.com

2 leds, 3 switch functions – ARI Armaturen ARI-PREMIO Plus EN User Manual

Page 27

background image

0040501004 5010

Page 27

Operating and installation instructions

Thrust actuator ARI-PREMIO-Plus

5.5.2 LEDs

5.5.3 Switch functions

LED

Colour

Meaning

Description / explanation

Green

Power

The electronics are connected to the power supply

Red

Failure

The actuator cannot reach the setpoint /
desired position

Orange

Function check

Blockage, manual mode
(handwheel or slide switch)

Yellow

Out of specification

This LED lights up if the following parameters are
exceeded:
- CDF (cyclic duty factor)
- Temperature range
- Travel
(during the initialisation run)
- Blinking during the initialisation run

Blue

Maintenance

This LED lights up if predefined limit values or
parameters are exceeded, depending on the
setting of the diagnostic switch.

NOTE !
Factory setting: All slide switches down.

Switch

Meaning

Description / explanation

Actuator control switches

Reset button or start /
cancel initialisation run

The Reset button re-launches the software and restores the
factory settings. Any faults that are stored are cleared
(blockage, etc.).
If you press the Reset button for longer than two seconds, the
actuator control starts an initialisation run. The yellow "Out of
specification" LED blinks as long as the initialisation run is
active. The actuator automatically travels to the two final
positions in order to determine the valve lift.
You can cancel the initialisation run by pressing the Reset
button again or by sliding the "MAN" switch.