5 interface description, 1 control - run commands – ARI Armaturen ARI-PREMIO Plus EN User Manual
Page 10

Page 10
0040501004 5010
Operating and installation instructions
Thrust actuator ARI-PREMIO-Plus
4.5 Interface description
4.5.1 Control - Run commands
Control
Desciption - Technical data
Required options
OPEN-STOP-CLOSE
(3-point)
2 Binary input
- 12V to 240V AC
- zero potential contacts
-
Modbus
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device adress: 0 ... 255
- Max. number of participants: 32
- dTRON316
with RS422/485 card
(dTRON options)
Profibus-DP
- Device adress: 0 ... 255
- dTRON316
with Profibus card (dTRON options)
Set point control for
position controller
4-20mA DC
- Burden 125 Ohm
- Resolution 10 Bit
- Electrically isolated
-
0-10V DC
- Burden 470 kOhm
- Resolution 10 Bit
- Electrically isolated
-
Modbus
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device adress: 0 ... 255
- Max. number of participants: 32
- dTRON316
with analog output card and RS422/485
card (dTRON options)
Profibus-DP
- Device adress: 0 ... 255
- dTRON316
with analog output card and Profibus
card (dTRON options)
Set point control for PID
process control (Option
dTRON 316)
4-20mA DC
- Burden 75 Ohm
- Resolution 10Bit
- dTRON316
with analog output card and analog
input card (dTRON options)
0-10V DC
- Burden > 100 kOhm
- Resolution 10 Bit
- dTRON316
with analog output card and analog
input card (dTRON options)
Modbus
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device adress: 0 ... 255
- Max. number of participants: 32
- dTRON316
with analog output card and RS422/485
card (dTRON options)
Profibus-DP
- Device adress: 0 ... 255
- dTRON316
with analog output card and Profibus
card (dTRON options)