Operating and installation instructions
Thrust actuator ARI-PREMIO-Plus
5.4.3 Connection
Fig. 13: The complete electronics are delivered on the board support
The following points should be taken into account in addition to the general principles
governing installation work:
- All electrical installation work carried out on the plant must comply with current regional
regulations.
- The mains voltage must match the information given on the rating plate of the thrust
actuator.
- Choose the optimum line cross-section according to the available driving power and line
length.
- Maximum mains fuse rating: 6 A.
- Circuit breaker in the plant to cut off the mains supply to the actuator.
ATTENTION !
- Work on electrical systems or equipment must only be carried out by qualified
electricians or by trained individuals under the guidance and supervision of a
qualified electrician in compliance with regional electrical requirement and
regulations.
- When connecting the electronics the supply line must be disconnected from the
mains (not live) during connection work. It must be impossible to switch the
power on unintentionally while the mains are disconnected in this way. Failure
to comply may result in death, serious injury or substantial damage to property.
- The mains voltage must coincide with the values indicated on the rating
plate.
- Never touch live parts while carrying out adjustments!
- Exercise particular caution when working with voltages higher than 24 V!
- Never insert or withdraw modular isolating terminals that are still live!
- Only one actuator can be connected.
- The actuator lift range must not be overtravelled when carrying out
adjustments; risk of damage.
- Make sure the motor connected in the actuator is switched off in the final
positions according to the travel or torque.