Hi-asn, Hi-t, Lo-asn – Red Lion PAX2S User Manual
Page 20: Lo-t, Dsp-t, At-t, At-bnd, Disply, Secondary function parameters ( scndry )

20
MAX (HI) CAPTURE ASSIGNMENT
rEL
GrOSS
Select the desired input value that will be assigned to the Max Capture.
MAX (HI) CAPTURE DELAY TIME
0.0
to
3275.0
seconds
When the Input value is above the present MAX value for the entered delay
time, the meter will capture that value as the new MAX reading. A delay time
helps to avoid false captures of sudden short spikes.
MIN (LO) CAPTURE ASSIGNMENT
rEL
GrOSS
Select the desired input value that will be assigned to the Min Capture.
MIN (LO) CAPTURE TIME
0.0
to
3275.0
seconds
When the Input value is below the present MIN value for the entered delay
time, the meter will capture that value as the new MIN reading. A delay time
helps to avoid false captures of sudden short spikes.
DISPLAY UPDATE RATE
1
2
5
10
20
updates/second
This parameter configures the display update rate. It does not affect the
response time of the setpoint output or analog output option cards.
AUTO-ZERO TRACKING TIME
0
to
250
seconds
To disable Auto-zero tracking, set this value to 0.
AUTO-ZERO TRACKING BAND
1
to
4095
The meter can be programmed to automatically compensate for zero drift.
Drift may be caused by changes in the transducers or electronics, or accumulation
of material on weight systems.
Auto-zero tracking operates when the readout remains within the tracking
band for a period of time equal to the auto-zero tracking time. When these
conditions are met, the meter re-zeroes the readout. After the re-zero operation,
the meter resets and continues to auto-zero track.
The auto-zero tracking band should be set large enough to track normal zero
drift, but small enough to not interfere with small process inputs.
For filling operations, the fill rate must exceed the auto-zero tracking rate.
This avoids undesirable tracking at the start of the filling operation.
Fill Rate ≥ tracking band
tracking time
Auto-zero tracking is disabled by setting the auto-zero tracking time
parameter = 0.
HI-ASN
rEL
SEC
HI-t
1.0
SEC
LO-ASN
rEL
SEC
LO-t
1.0
SEC
dSP-t
2
SEC
At-t
0
SEC
At-bnd
0.02
SEC
HI-ASN
rEL
SEC
HI-t
1.0
SEC
LO-ASN
rEL
SEC
LO-t
1.0
SEC
MAX Capture
Assignment
MAX Capture
Time
MIN Capture
Assignment
MIN Capture
Time
dISPLY
SCNdrY
At-t
0
SEC
dSP-t
2
SEC
Display
Update Rate
Auto-Zero
Tracking Time
At-bnd
0.02
SEC
Auto-Zero
Tracking Band
Pro
dISPLY
Pro
NO
F1
F2
P
D
SECONDARY FUNCTION PARAMETERS (SCNdrY)