HP Modular Cooling System User Manual

Page 45

background image

Cooling performance parameter settings 45

IMPORTANT:

Temperature Control Manual mode is for service and troubleshooting only and is

not to be used in a production environment.

Parameter Function

Temperature

Control

Used in Auto mode to determine if the MCS unit operates

in Auto mode or Manual mode

Fan Speed Target Used in Manual mode to increase or decrease the fan

speed level

Water Valve

Used in Manual mode to vary the opening percentage of
the water valve in Manual mode

Delta Temperature
for Minimum Fan

Speed

Used in Auto mode to set the maximum delta
temperature when the Minimum Fan Speed will be used

Delta Temperature
for Maximum Fan

Speed

Used in Auto mode to set the minimum delta temperature
when the Maximum Fan Speed will be used

Cooling Liquid
Heat Capacity

(Cw) Value

Used in Auto mode to calculate the energy extracted by
the air to water heat exchanger unit (This value for pure

water is 4,187 Ws/kg and can be a lower value if

additives are included in the water.)

Delta temperature (Server Intake Temp/Server Exhaust Temp)

Delta temperature is calculated from the temperature difference between the server intake temperature

and server exhaust temperature. The server intake temperature, or cold air, is the air coming from the heat
exchanger unit and pushed through the fan units. The server exhaust temperature, or hot air, is the air

coming from the fan units and being pushed through the heat exchanger unit.
Example

Server intake
temperature

Server exhaust
temperature