HP Modular Cooling System User Manual
Page 17
Web interface 17
Solution:
1.
Verify water supply and that the MCS unit is receiving water.
2.
Verify that the High Temperature Emergency Door Opening Threshold is not less than 5°C (41°F)
above or more than 20°C (68°F) above the Server Intake Temperature Set Point, or that it is not
below the Water Flow Loss Emergency Door Opening Temperature Threshold.
3.
Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
Door Opening Temperature Threshold fields to prevent false alarms.
IMPORTANT:
Use caution when entering temperatures in the Emergency Door Opening fields.
Setting the temperature thresholds too low might cause the MCS unit to shut down.
The condensation pump has exceeded x cycles
Indicators Meaning
Operator display alarm message Excessive Moisture
Web interface alarm message
The condensation pump has exceeded x cycles
Condition
The water level has exceeded the permissible level of the condensation
pump sensor
Modules or sensors
Condensation pump sensor
SNMP notification
Warning
Type of message
Warning
Solution:
1.
Look for leaks or determine if condensation is the cause.
2.
If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Cycles
Warning Threshold field.
IMPORTANT:
Use caution when entering temperatures in the Condensation Pump Threshold
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat
load generated by the equipment in the MCS.
The condensation pump has run more than x seconds
Indicators Meaning
Operator display alarm
message
Excessive Moisture
Web interface alarm
message
The condensation pump has run more than x seconds
Condition
The water level has exceeded the permissible level of the condensation pump sensor.
Modules or sensors
Condensation pump sensor
SNMP notification
Warning
Type of message
Warning
Solution:
1.
Look for leaks or determine if condensation is the cause.