beautypg.com

Identification menu – HP Modular Cooling System User Manual

Page 18

background image

Web interface 18

2.

If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running

Time Warning Threshold field.

IMPORTANT:

Use caution when entering temperatures in the Condensation Pump Threshold

fields. Be sure to determine the proper default settings to prevent false alarms, without masking

problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat
load generated by the equipment in the MCS.

NOTE:

A 24-hour clock starts when the condensation pump runs for the first time in more than

24 hours. A warning is issued if either the cycle threshold or pump running time is exceeded

within the 24-hour window. The clock stops and the counters are reset to zero for warning

purposes if the thresholds are not exceeded within 24 hours after the last time the

condensation pump runs.

NOTE:

To clear the condensation pump cycles warning, click Cooling System in the left

navigation frame to access the Cooling System screen, and then click the Alarms/Warnings

tab. Under the Warnings section, set Alarm Reset to Manual and click Save Settings. Then,
return to the General menu and click Clear Alarms.
This step only clears the warning when the condensation pump is not running.

Identification menu

Click Identification in the left navigation frame to display the Identification screen. This screen displays

specific device and contact information.
You can enter or change the system name, system contact, and system location information in the System

Information tab (on page

34

).

You can change the IP address in the Network menu (on page

32

).