Identification menu – HP Modular Cooling System User Manual
Page 18
Web interface 18
2.
If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running
Time Warning Threshold field.
IMPORTANT:
Use caution when entering temperatures in the Condensation Pump Threshold
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat
load generated by the equipment in the MCS.
NOTE:
A 24-hour clock starts when the condensation pump runs for the first time in more than
24 hours. A warning is issued if either the cycle threshold or pump running time is exceeded
within the 24-hour window. The clock stops and the counters are reset to zero for warning
purposes if the thresholds are not exceeded within 24 hours after the last time the
condensation pump runs.
NOTE:
To clear the condensation pump cycles warning, click Cooling System in the left
navigation frame to access the Cooling System screen, and then click the Alarms/Warnings
tab. Under the Warnings section, set Alarm Reset to Manual and click Save Settings. Then,
return to the General menu and click Clear Alarms.
This step only clears the warning when the condensation pump is not running.
Identification menu
Click Identification in the left navigation frame to display the Identification screen. This screen displays
specific device and contact information.
You can enter or change the system name, system contact, and system location information in the System
Information tab (on page
You can change the IP address in the Network menu (on page