Web interface 11

Indicators Meaning

Operator display alarm message Fan 1, 2, 3, 4, 5, or 6 Failed
Web interface alarm message

Fan 1, 2, 3, 4, 5, or 6 Failed/ Not installed

Condition

Fan 1, 2, 3, 4, 5, or 6 is less than its minimum rpm

Module

Fan 1, 2, 3, 4, 5, or 6

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Remove the fan unit.

2.

Reinstall the same fan unit.

If the warning message does not clear after the module is reseated, replace the fan unit with a CSR part.

For more information on CSR parts, see "Replaceable parts and maintenance and service information (on

page

54

)."

HEX (heat exchanger unit) temperature in failed (Server Intake Temperature failed)

Indicators Meaning

Operator display alarm message HEX1, HEX2, or HEX3 Temp. In Failed
Web interface alarm message

Top Heat Exchanger Intake Air Temperature Sensor to Server Failed

Condition

Temperature reading is beyond limit (possible open circuit)

Sensors

HEX1, HEX2, or HEX3 sensors (this is the water to air heat exchanger unit

temperature of the intake to the servers)

SNMP notification

Warning

Type of message

Warning

Solution:
Contact HP, or see the HP website (

http://www.hp.com

).

HEX temperature out failed (Server Exhaust Temperature failed)

Indicators Meaning

Operator display alarm message HEX1, HEX2, or HEX3 Temp. Out Failed
Web interface alarm message

Top Heat Exchanger Exhaust Air Temperature Sensor from Server Failed

Condition

Temperature reading is beyond limit (possible open circuit)

Sensors

FAN 1, 2, 3, 4, 5 or 6 sensors (this is the fan unit temperature of the
exhaust from the servers)

SNMP notification

Warning

Type of message

Warning

Solution:
Contact HP, or see the HP website (

http://www.hp.com

).

Low water flow