beautypg.com

Cooling performance parameter settings, Cooling performance parameter settings overview – HP Modular Cooling System User Manual

Page 43

background image

Cooling performance parameter settings 43

Cooling performance parameter settings

Cooling performance parameter settings overview

The MCS unit has several cooling performance parameter settings. These settings control the fan speed
and water flow to meet the cooling needs of the rack-mounted components.
The temperature of the server intake air is controlled by varying the opening percentage of the water

valve inside the MCS unit. When the server intake air temperature is above the Server Intake Temperature

Set Point, the opening percentage of the water valve increases. When the server intake air temperature is
below the Server Intake Temperature Set Point, the opening percentage of the water valve decreases.
The level of speed for each fan unit is controlled through the control system using the server intake and

server exhaust temperatures.

Parameter Function

Server Intake
Temperature Set

Point

Used to control the desired air temperature going into
the front of the servers

High Temperature

Threshold

Used to issue a Critical alarm if the high temperature

threshold temperature is exceeded

Warning
Temperature

Threshold

Used to issue a warning if the warning temperature
threshold temperature is exceeded

Low Temperature
Threshold

Used to issue a warning if the low temperature threshold
temperature is exceeded