Cooling performance parameter settings 44

Parameter Function

Water Flow Loss
Emergency Door

Opening
Temperature

Threshold

Used to open the MCS doors when the temperature
threshold is exceeded and water loss is detected
This value cannot be lower than 5°C (41°F) above or

more than 20°C (68°F) above the Server Intake
Temperature Set Point.

High Temperature
Emergency Door

Opening Threshold

Used to open the MCS doors when the temperature
threshold is exceeded
This value:

Cannot be lower than 5°C (41°F) above or more
than 20°C (68°F) above the Server Intake

Temperature Set Point.

Cannot be less than the Water Flow Loss Emergency

Door Opening Temperature Threshold.

Excessive
Moisture:

Condensation

Pump Cycles
Warning

Threshold

Used to issue a warning if the condensation pump
exceeds the permissible number of cycles within a 24-

hour period

Excessive
Moisture:

Condensation

Pump Running
Time Warning

Threshold

Used to issue a warning if the condensation pump has
run longer than the permissible running time

Alarm Relay

Used to enable or disable the alarm relay

Audible Alarm

Used to enable or disable the audible alarm

Alarm Reset

Used to enable the alarm to be reset automatically (Auto)
or manually (Manual)

Trap Receiver

Used to activate trap receivers 1 through 4

Server Intake
Temperature Trap

Message Text

Used to enter information that displays when a server
intake temperature trap is received