Indicators Meaning
Operator display alarm message Water flow Sensor ?
Web interface alarm message
Water flow Sensor Value Out of Range
Condition
Water flow sensor is not working properly
Sensor Water
group
SNMP notification
Warning
Type of message
Warning
Solution:
1.
Verify the water supply.
2.
Contact HP, or see the HP website (
Water flow valve is closed
Indicators Meaning
Operator display alarm message Water Valve ?
Web interface alarm message
Water Valve Failed
Condition
Water flow valve is closed and water flow is detected
Modules Water
group
SNMP notification
Warning
Type of message
Warning
Solution:
1.
Verify the water valve is closed.
2.
Contact HP, or see the HP website (
Leak detector sensor is not working properly
Indicators Meaning
Operator display alarm message Leak detector?
Web interface alarm message
Leak detector Failed
Condition
Leak detector sensor is not working properly
Sensors
Leak detector sensor
SNMP notification
Warning
Type of message
Warning
Solution:
Contact HP, or see the HP website (
Uneven heat load
Indicators Meaning
Operator display alarm message Heat Load?
Web interface alarm message
Heat Load Warning
Condition
Measured air temperature values dramatically different from top to bottom