LED display with the technology unit:
The status of the PROFIBUS technology unit is indicated by the two built-in LEDs:
Green LED
BR Bus Ready
Red LED
BE Bus Error
Meaning
... slow flashing = 1Hz (1s cycle), rapid flashing = 2Hz (0.5s cycle)
ON
OFF
Normal operation; cyclic transfer of data via the PROFIBUS.
ON
ON
Faulty operation; e.g. the PPO type was changed during operation.
Slow flashing
OFF
Process data has not yet been received after switch-on
e.g. no connection to master
Slow flashing
Brief illumination
Initialisation of the PROFIBUS module (on switch-on or change to
a Profibus parameter on the frequency inverter)
Slow flashing
ON
Timeout in process data reception: the Watchdog time
parameterised in the Profibus master has expired without the
reception of new process data for a maximum of 3s (e.g. baud rate
not detected, cable break).
Slow flashing
Slow flashing
Timeout in process data reception: The time set in P513 has
expired without new process data being received
Slow flashing
Rapid flashing
software version 3.3 R0 and
above
Communication between the
inverter and the PROFIBUS
module has been interrupted.
ON
Slow flashing
up to software version 3.2 R0