PROFIBUS DP
– Supplementary manual options for NORD - Frequency Inverters
22
BU 0020 GB-2612
2.2.5 Profibus module, SK CU1-PBR (and SK 750E)
In addition to data connections, the Profibus customer units are also
equipped with conventional digital inputs and outputs. The
SK CU2-PBR can be used in both the SK 700E and the SK 750E
series.
By means of a relay contact, brake control and even warnings to
another system can be initiated.
Various digital functions can be programmed for the input. The
digital input has a 2.5V switching threshold for the evaluation of the
temperature sensor.
The bus termination resistor (R
ab
) can be switched in. For this, both
switches must be set to 'On'. A transfer rate of up to 1.5Mbit/s can
be used.
Profibus,
SK CU1-PBR
Functions
Maximum cross-
section
X6.1
Output relay
1.5 mm
2
X6.2
Digital input
1.5 mm
2
X6.3
Data cables
1.5 mm
2
X6.4
Data cables, parallel
1.5 mm
2
Detail:
DIP switch
Assembly
Description
Data
Profibus module
SK CU1-PBR
This option enables control of the SK 700E/750E via the
Profibus DP interface with the performance level DP-V0
Baud rate: up to 1.5
MBaud
1 x digital input
1 x output relay
Direct plugs, terminals
and connectors
Part No. 278200030
Table 4: SK CU1-PBR, overview of customer units
Note
The cable shield must be connected to the functional earth
3
(usually the
electrically conducting mounting plate) in order to avoid EMC interference in the
device.
With the two SK 8 shield terminals enclosed with option, the Profibus cables can be
connected to the shield bracket of the frequency inverter.
Pos: 36 /Anleitungen/Bussysteme/2. Baugruppen/Profibus [BU0020]Klemmenbelegung SK CU1-PBR @ 1\mod_1335342550420_388.docx @ 22231 @ 5 @ 1
3
In systems, electrical equipment is usually connected to a functional earth. This serves as a means to dissipate leakage and
interference currents in order to ensure EMC characteristics and must therefore be implemented according to high frequency
technology aspects.