NORD Drivesystems BU0020 User Manual
Page 76
PROFIBUS DP
– Supplementary manual options for NORD - Frequency Inverters
76
BU 0020 GB-2612
Bit
Value
Meaning
Remarks
0
0
Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1
0
Not ready for operation Causes: No command has been activated, fault is signaled, OFF2 or OFF3
activated, starting disabled state activated
1
Ready for operation
ON command activated, no faults present. The inverter can be started with the
command ENABLE OPERATION
2
0
Operation disabled
1
Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3
0
No fault
1
Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after
the fault has been successfully acknowledged
4
0
OFF 2
OFF2 command applied
1
No OFF 2
5
0
OFF 3
OFF3 command applied
1
No OFF 3
6
0
Starting not disabled
1
Starting disabled
Switches first to OFF1, then to ready-to-start status
7
0
No warning
1
Warning
Drive operation continues, no acknowledgement necessary
8
0
Actual value not O.K.
Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)
1
Actual value O.K.
Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached)
9
0
Local guidance
Guidance on local device has been activated
1
Guidance requested
The master has been requested to assume guidance.
10
0
1
SK 5xxE:
Bit 10 active
Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481.
SK 300E / 7x0E:
MFR 1 reference value
reached
Programmed function of the MFR 1 is fulfilled, or
Actual value ≥ programmed reference value
11
0
1
Rotational
direction:
right
Inverter output voltage is turning right
12
0
1
Rotational
direction:
left
Inverter output voltage is turning left
13
0
1
SK 5xxE:
Bit 13 active
Bus bit 13 from the status word is set. For further details of function, please refer
to parameter P481.
SK 7x5E:
MFR 4 reference value
reached
Only with Posicon extension: Status MFR 4 = 1
14
0/1
Currently active
parameter set 0
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Currently active
parameter set 1
Pos: 130 /Anleitungen/Bussysteme/6. Datenübertragung/Sollwert 1 (SW1) @ 1\mod_1336390248316_388.docx @ 25543 @ 355 @ 1