P746 module status, P746, Module status – NORD Drivesystems BU0020 User Manual
Page 60
PROFIBUS DP
– Supplementary manual options for NORD - Frequency Inverters
60
BU 0020 GB-2612
P746
Module status
(Module status)
SK 300E
S
0000 ... FFFF (hex)
Shows the actual status (readiness, error, communication) of the technology unit (SK TU2-xxx),
but only when own processor is present, i.e. not for SK TU2-CTR.
Example:
0603
hex
High byte = 06
hex
Profibus
Low byte = 03
hex
Module ready + connection to master
Details of the codes specific to the bus can be found in the section "Error monitoring" of the
relevant supplementary instructions.
Pos: 91 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P746
– Baugruppen Zustand [SK 7x0E] @ 1\mod_1335792880284_388.docx @ 25144 @ @ 1
P746
[-01]
...
[-03]
Module status
(Module status)
SK 7x0E
S
0000 ... FFFF (hex)
Shows the actual status (readiness, error, communication) of
the installed technology unit(s) (if active), but only when own
processor is present, i.e. not for SK TU1-CTR.
Example:
0603
hex
High byte = 06
hex
Profibus
Low byte = 03
hex
Module ready + connection to master
Details of the codes specific to the bus can be found in the
section "Error monitoring" of the relevant supplementary
instructions.
[-01] = Technology unit
[-02] = Customer unit
[-03] = Special extension unit