6 Parameterisation
BU 0020 GB-2612
59
6.1.3 Information
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter set
Pos: 86 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P740
– Prozessdaten Bus In [SK 300E, SK 7x0E] @ 1\mod_1335791131327_388.docx @ 25024 @ @ 1
P740
[-01]
...
[-06]
Process data Bus In
(Process data bus in)
SK 300E /
SK 7x0E
S
0000 ... FFFF (hex)
This
parameter
informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.
For display, a BUS system
must be selected in P509
Series SK 300E:
[-01 ] = Control word
Series SK 7x0E:
[-01 ] = Control word
[-02] = setpoint value 1
[-03] = setpoint value 2
[-04] = setpoint value 3
[-02] = setpoint value 1
[-03] = Setpoint value 1 High
byte
[-04] = setpoint value 2
[-05] = setpoint value 3
[-05] = Bus I/O In Bits (P480)
[-06] = Bus I/O In Bits (P480)
Pos: 87 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P741
– Prozessdaten Bus Out [SK 300E / SK 7x0E] @ 1\mod_1335791437905_388.docx @ 25048 @ @ 1
P741
[-01]
...
[-06]
Process data Bus Out
(Process data bus out)
SK 300E /
SK 7x0E
S
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.
Series SK 300E
[-01] = Status word
Series SK 7x0E
[-01] = Status word
[-02] = Actual value 1
[-03] = Actual value 2
[-04] = Actual value 3
[-02] = Actual value 1
[-03] = Actual value 1 High
byte
[-04] = Actual value 2
[-05] = Actual value 3
[-05] = Bus I/O Out Bit (P481)
[-06] = Bus I/O Out Bit (P481)
Pos: 88 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P745
– Baugruppen Version [SK 300E] @ 1\mod_1335791798489_388.docx @ 25072 @ @ 1
P745
Module version
(Module version)
SK 300E
0.0 ... 3276.7
Version status (software version) of the technology unit (SK TU2-xxx), but only when own
processor is present, i.e. not for SK TU2-CTR.
Have this data available if you have a technical query.
Pos: 89 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P745
– Baugruppen Version [SK 7x0E] @ 1\mod_1335792003777_388.docx @ 25096 @ @ 1
P745
[-01]
...
[-03]
Module version
(Module version)
SK 7x0E
S
0000 ... FFFF (hex)
Version status (software version) of the installed option
module(s) but only when own processor is present, i.e. not for
SK TU1-CTR.
Have this data available if you have a technical query.
[-01] = Technology unit
[-02] = Customer unit
[-03] = Special extension unit
Pos: 90 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P746
– Baugruppen Zustand [SK 300E] @ 1\mod_1335792492116_388.docx @ 25120 @ @ 1