P509 interface, P510 bus interface auxiliary setpoint, P513 telegram time-out – NORD Drivesystems BU0020 User Manual
Page 56
PROFIBUS DP
– Supplementary manual options for NORD - Frequency Inverters
56
BU 0020 GB-2612
P509
Interface
(Interface)
0 ... 21
{ 0 }
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control ** with the ControlBox (if P510=0), the
ParameterBox (not ext. P-box) or via BUS I/O Bits.
1 = Only control terminals , the FI can only be controlled via the digital and analog
inputs or via the bus I/O Bits.
8 = Profibus setpoint, the frequency setpoint is transferred via Profibus. Control via the
digital inputs is still active.
9 = Profibus control word, the control signals (enable, direction of rotation, ...) are
transferred via Profibus, the setpoint via the analog input or the fixed frequencies.
10 =
Profibus, all control data is transferred via Profibus. The analog input and the digital
inputs have no function (except safety functions)
*) Keyboard control (ControlBox, ParameterBox, PotentiometerBox) is blocked,
parameterisation is still possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec),
the FI will block without an error message.
Pos: 77 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P510
– Schnittstelle Busnebensollwerte [SK 700E] @ 1\mod_1335780555886_388.docx @ 24850 @ @ 1
P510
Bus interface auxiliary setpoint
(Bus interface auxiliary setpoints)
SK 700E/
SK750E
S
0 ... 8
{ all 0 }
Selection of the interface via which the FI is controlled.
0 = Auto (=P509): The source of the auxiliary setpoint is automatically derived from the
setting in the parameter P509 >Interface<
1 = USS
2 = CANbus
3 = Profibus
4 = InterBus
5 = CANopen
6 = DeviceNet
7 = Reserved
8 = CAN Broadcast
Pos: 78 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P513
– Telegrammausfallzeit @ 0\mod_1328092407709_388.docx @ 11180 @ @ 1
P513
Telegram time-out
(Telegram time out)
S
-0.1 / 0.0 /
0.1 ... 1000 s
{ 0.0 }
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an error and switches off with the error
message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = No error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
Pos: 79 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P543
– Bus-Istwert 1 [SK 300E, SK 7x0E] @ 1\mod_1335781763553_388.docx @ 24880 @ @ 1