P741, Pzd bus out – NORD Drivesystems BU0020 User Manual
Page 68
PROFIBUS DP
– Supplementary manual options for NORD - Frequency Inverters
68
BU 0020 GB-2612
P741
[-01]
...
[-13]
PZD bus out
(Process data bus out)
up to SK 535E
S
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.
[-01] = Status word
Status word, source from
P509.
[-02] = Actual value 1 (P543)
[-03] = Actual value 2 (P544)
[-04] = Actual value 3 (P545)
[-05] = Bus I/O Out Bit (P481)
The displayed value depicts
all Bus In bit sources linked
with OR.
[-06] = Parameter data Out 1
[-07] = Parameter data Out 2
[-08] = Parameter data Out 3
[-09] = Parameter data Out 4
[-10] = Parameter data Out 5
Data during parameter
transfer.
[-11] = Actual value 1 leading
function
[-12] = Actual value 2 leading
function
[-13] = Actual value 3 leading
function
Actual value of leading
function P502/P503.
Pos: 116 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P741
– Prozessdaten Bus Out [ab SK 540E] @ 0\mod_1328177956772_388.docx @ 13382 @ @ 1
P741
[-01]
...
[-23]
PZD bus out
(Process data bus out)
SK 540E and
above
S
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.
[-01] = Status word
Status word, source from
P509.
[-02] = Actual value 1 (P543 [-01])
[-03] = Actual value 2 (P543 [-02])
[-04] = Actual value 3 (P543 [-03])
[-05] = Actual value 4 (P543 [-04])
[-06] = Actual value 5 (P543 [-05])
[-07] = Bus I/O Out Bit (P481)
The displayed value
depicts all Bus In bit
sources linked with OR.
[-08] = Parameter data Out 1
[-09] = Parameter data Out 2
[-10] = Parameter data Out 3
[-11] = Parameter data Out 4
[-12] = Parameter data Out 5
Data during parameter
transfer.
[-13] = Actual value 1 leading function
[-14] = Actual value 2 leading function
[-15] = Actual value 3 leading function
[-16] = Actual value 4 leading function
[-17] = Actual value 5 leading function
Actual value of leading
function P502/P503.
[-18] = PLC status word
Status word via PLC
[-19] = Actual value 1 PLC
[-20] = Actual value 2 PLC
[-21] = Actual value 3 PLC
[-22] = Actual value 4 PLC
[-23] = Actual value 5 PLC
Actual value data via PLC
Pos: 117 /Anleitungen/5. Parametrierung/Parameter/P700-P799/Parameter P745
– Baugruppen Version @ 0\mod_1328178182499_388.docx @ 13474 @ @ 1