6 Error monitoring and error messages
36
BU 2200 GB-3813
Error code
Error register
FI Error Code (error number P700) *
0x9000
1
12.0 / 12.1 / 12.2
0xFF10
129
18.0
0xFF11
129
19.0
* For the meaning, refer to the frequency inverter manual.
Table 20: Assignment of BUS errors to inverter errors
Pos : 82 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/F ehl er mel dungen Et her net Baugruppen allgemein [ SK xU x-EI P / PO L - Allgemei n] @ 3\ mod_1363779786491_388. doc x @ 61865 @ 5 @ 1
Error messages
Error messages from the module - present errors or archived messages relating to the last error - can
be read out via the module parameter (P170). The error messages are lost if the module is switched
off.
Error
Meaning
Remarks
100.0
EEPROM error
EMC fault, module defective
102.0
Timeout
via P151/P513 monitoring
103.0
System bus BUS OFF
No 24V supply to the bus, connections not correct
104.0
Module temperature > 97°C
Only SK CU4-
…
550.1
DIP switch error
The DIP switches (IP address) could not be read correctly
560.0 …
560.9
Internal error
Module not ready
561.0
General network error
561.1
Ethernet Watchdog timeout
561.2
Bus cable fault
Bus cable connection interrupted
561.3
IP address error
IP address of the module has been doubly assigned
563.0
Firmware version incompatible
The firmware version cannot be used for the device
564.0
MAC address error
Errors which occur in relation to the module are depicted as follows in the error memory of the
frequency inverter (P700 / P701).
Error
(E010)
Meaning
Remarks
10.0
Connection error
Contact to SK xU4 lost
10.1
ASIC errors
Communication to Ethernet - ASIC lost
•
Switch-off of the supply voltage
10.2
Ethernet/IP Watchdog timeout
Telegram transfer error
•
Check the connections and links, program sequence and
Bus Master
10.3
Timeout by P151/P513
Telegram transfer error
•
Check the connections and links
•
Check the Watchdog time
10.4
IP address error
IP address of the module has been doubly assigned
10.5
Internal error
Module not ready,
•
for SK CU4
-
… e.g.: Module temperature > 97°C
10.6
Bus cable fault
Bus cable connection interrupted
10.8
The connection between the inverter
and the module had a timeout
Only SK TU3 module
10.9
The connection between the inverter
and the module had a timeout
Only SK xU4 module