Table 7: status word (zsw) – NORD Drivesystems BU2200 User Manual
Page 15
POWERLINK Bus module
–
Supplementary manual options for NORD - Frequency Inverters
BU 2200 GB-3813
15
Bit
Valu
e
Meaning
Remarks
0
0
Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1
0
Not ready for operation
Causes: No command has been activated, fault is signaled, OFF2 or OFF3
activated, starting disabled state activated
1
Ready for operation
ON command activated, no faults present. The inverter can be started with the
command ENABLE OPERATION
2
0
Operation not enabled
1
Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3
0
No error
1
Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after
the fault has been successfully acknowledged
4
0
Voltage not enabled
OFF2 command applied
1
Voltage enabled
5
0
Emergency stop
OFF3 command applied
1
No emergency stop
6
0
Starting not disabled
1
Starting disabled
Switches first to OFF1, then to ready-to-start status
7
0
No warning
1
Warning active
Drive operation continues, no acknowledgement necessary
8
0
Setpoint not reached
Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)
1
Setpoint reached
Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached)
9
0
Bus control not active
Guidance on local device has been activated
1
Bus controller active
The master has been requested to assume guidance.
10
0
1
Start function 481.9
Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481.
11
0
1
Rotation right is on
Inverter output voltage is turning right
12
0
1
Rotation left is on
Inverter output voltage is turning left
13
0
1
Start function 481.10
Bus bit 13 from the status word is set. For further details of function, please refer
to parameter P481.
14
0/1
Parameter set Bit 0 ON
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Parameter set Bit 1 ON
Table 7: Status word (ZSW)