beautypg.com

Process data bus out, Mac adddress, Nmt state – NORD Drivesystems BU2200 User Manual

Page 29: Nmt error

background image

POWERLINK Bus module

Supplementary manual options for NORD - Frequency Inverters

BU 2200 GB-3813

29

P177

... [-01]

... [-25]

Process Data Bus Out

(Process data Bus Out)

SK TU3-

SK xU4-

16 bit

-32768 ... 32767

Bus data sent from Bus Master / Controller.

[-01] = Bus module inputs*

[-02] = Status word FI 1

[-03] = Actual value 1 from FI 1

[-04] = Actual value 2 from FI 1

[-05] = Actual value 3 from FI 1

[-06] = Actual value 4 from FI 1

[-07] = Actual value 5 from FI 1

[-08] = Status word FI 2*

[-09] = Actual value 1 from FI 2*

[-10] = Actual value 2 from FI 2*

[-11] = Actual value 3 from FI 2*

[-12] = Actual value 4 from FI 2*

[-13] = Actual value 5 from FI 2*

[-14] = Status word FI 3*

[-15] = Actual value 1 from FI 3*

[-16] = Actual value 2 from FI 3*

[-17] = Actual value 3 from FI 3*

[-18] = Actual value 4 from FI 3*

[-19] = Actual value 5 from FI 3*

[-20] = Status word FI 4*

[-21] = Actual value 1 for FI 4*

[-22] = Actual value 2 for FI 4*

[-23] = Actual value 3 for FI 4*

[-24] = Actual value 4 for FI 4*

[-25] = Actual value 5 for FI 4*

* Except for SK TU3 versions

Pos : 66 /Anl eitungen/ Elektroni k/ Bus s yst eme/5. Par ameter/ P18x I nf ormati ons Paramet er

– Bus , s pezifisc h @ 3\mod_1369135411634_388.doc x @ 70043 @ 5 @ 1

Bus-specific Information Parameters (P18x)

Parameter

Setting value / Description / Note

Device

Type

Pos : 67 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/Bus übergreif end [ P150 ff. - P180 ff. ]/Par amet er P181

– MAC Adres se [SK xU x-... EIP, POL] @ 3\mod_1369127005384_388.doc x @ 69824 @ @ 1

P181

... [-01]

... [-06]

MAC Adddress

(MAC Address)

SK TU3-

SK xU4-

8 bit

0 ... 0xFF

Displays the Ethernet (MAC) address (unique identification of module)

[-

01] … [-03] = NORD manufacturer ID

F0 . 5F . 5A

[-

04] … [-06] = NORD address range

xx . xx . xx

Pos : 68 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/PO WER LIN K/ Par amet er P182

– NMT State [SK xU x- POL] @ 4\mod_1378889909332_388.doc x @ 94586 @ @ 1

P182

NMT State

(NMT Status)

SK TU3-POL

SK xU4-POL

8 bit

0 ... 0xFF

Status of the Control Node

0x09 = INITIALISATION

0x19 = INITALISING

0x1C = NOT ACTIVE

0x1D = PRE_OPERATIONAL_1

0x1E = BASIC_ETHERNET

0x29 = RESET_APPLICATION

0x39 = RESET_COMMUNICATION

0x4D = STOPPED

0x5D = PRE_OPERATIONAL_2

0x6D = READY_TO_OPERATE

0x79 = RESET_CONFIGURATION

0xFD = OPERATIONAL

Pos : 69 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/PO WER LIN K/ Par amet er P183

– NMT Error [SK xU x- POL] @ 4\mod_1378890692610_388.doc x @ 94610 @ @ 1

P183

NMT Error

(NMT Error)

SK TU3-POL

SK xU4-POL

16 bit

0 ... 65535

Error of the Control Node Please refer to the POWERLINK specification DS301 (App.3.10) for
the meaning of the codes.

Pos : 70 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/PO WER LIN K/ Par amet er P184

– NMT Statec hangec ount [SK xU x-POL] @ 4\mod_1378890895566_388.doc x @ 94634 @ @ 1