5 Parameter
24
BU 2200 GB-3813
5. Parameter
In order to operate the frequency inverter on the bus system, some parameter settings must be made
on the bus interface and on the frequency inverter.
The frequency inverter can always be parameterised. The control source can be selected with
parameter P509 (control word) and parameter P510 (setpoint source). The telegram down time P513
can be selected depending on the bus system.
Information
Deviating Parameter Settings
According to the type or equipment of the frequency inverter, individual parameters may be different or restricted.
Information
Control terminal functions
When activated, the functions block voltage, quick stop, remote control and cancel error, are available at the
(local) control terminals. To operate the drive, a High signal must be present on the digital inputs being used
before the drive can be enabled.
Pos : 43 /Anl eitungen/ Elektroni k/ Bus s yst eme/5. Par ameter/ Parameter Bus - Baugruppe [allgemein] @ 3\ mod_1369220113978_388.doc x @ 70535 @ 2 @ 1
5.1 Bus - Module Parameters
Pos : 44 /Anl eitungen/ Elektroni k/ Bus s yst eme/5. Par ameter/ P15x Standard Paramet er - Bus @ 3\ mod_1369132027784_388. doc x @ 69971 @ 5 @ 1
Standard Bus Parameter (P15x)
Parameter
{Factory seting}
Setting value / Description / Note
Device
Type
Pos : 45 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/Bus übergreif end [ P150 ff. - P180 ff. ]/Par amet er P150
– R elais setzen [SK TU 4- xxx, SK EBIOE] @ 3\mod_1368690523747_388.doc x @ 65202 @ @ 1
P150
Set Relay
(Set relay)
SK
EB…
SK TU4-
…
8 bit
0 ... 4
{ 0 }
The switching statuses of the digital outputs can be modified.
0 =
Via Bus:
All digital outputs can be controlled via the system bus: the
fucntions are defined in the frequency inverter (P480).
1 =
Outputs Off:
All digital outputs are Off (Low = 0V).
2 =
Output 1 On (DO1):
The digital output DO1 is set to "High" (active); digital
output DO2 remains switched off.
3 =
Output 2 On (DO2):
The digital output DO2 is set to "High" (active); digital
output DO1 remains switched off.
4 =
Outputs 1 and 2 On:
All digital outputs are set to "High" (active)
Pos : 46 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/Bus übergreif end [ P150 ff. - P180 ff. ]/Par amet er P151
– Ti meOut externer Bus [SK xU4- xxx] @ 3\mod_1368691795097_388.doc x @ 65639 @ @ 1
P151
External Bus Timeout
(Timeout for external bus)
SK xU4-
…
16 bit
0 ... 32767 ms
{ 0 }
Monitoring function of the active bus technology unit. Following receipt of a valid telegram, the
next one must arrive within the set period. Otherwise the technology unit or the connected
inverter reports an error and switches off with the error message E010 / E10.3 >Bus Time Out<.