Parameter transfer, Table 14: device assignment to sdo-id, Information – NORD Drivesystems BU2200 User Manual

Page 21: 4 parameter transfer, Sdo handling

background image

POWERLINK Bus module

Supplementary manual options for NORD - Frequency Inverters

BU 2200 GB-3813

21

1

2

3

4

5

Address

0x5001.4

0x5003.10

0x5003.11

0x5003.12

0x5003.13

0x5003.14

Table 11: PDO Mapping / Process Data Structure SK XU4-POL

The allocation of the values transferred in the setpoint/actual value area of the FI is made via the
parameters P543 to P548 or P543 / P546 [-

01]…[-05].

Pos : 38 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /POWER LIN K [ BU 02200]/Digital e I Os ( nur SK xU 4-PO L) [SK xU 4-POL] @ 4\ mod_1379405545871_388.doc x @ 98586 @ 5 @ 1

Digitale IOs (only SK xU4-POL)

The SK TU4-POL is equipped with 8 digital inputs and 2 digital outputs. In contrast, the SK CU4-POL
only has 2 digital inputs. These can be controlled or read via process data word 1.

Inputs (status value)

A 16 bit word is transferred. The 8 (or 2) inputs are located in the Low byte and the High byte on Bit 15
contains the "Valid Flag" for the inputs. The transferred inputs are only valid if this flag is set to 1.

Module

High byte

Low byte

Bit 15

Bit 14 to 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

SK TU4-POL

Valid Flag

Reserve

DIN8

DIN7

DIN6

DIN5

DIN4

DIN3

DIN2

DIN1

SK CU4-POL

Valid Flag

Reserve

Reserve

DIN2

DIN1

Table 12: Structure of the Input Word in the Process Data

Outputs (Setpoint)

The SK TU4-POL is equipped with 2 digital 24V outputs. The outputs can be set with a 16 bit word.

Module

High byte

Low byte

Bit 15 to 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

SK TU4-POL

Reserve

Reserve

DO2

DO1

SK CU4-POL

Reserve

Reserve

Table 13: Structure of the Output Word in the Process Data

Pos : 39 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /POWER LIN K [ BU 02200]/Paramet erübertragung [- PO L] @ 4\ mod_1378738489191_388. doc x @ 93858 @ 255 @ 1

4.4 Parameter transfer

All parameters of the bus module and the
connected frequency inverter can be
accessed via POWERLINK. Access is via
objects (SDO).

Object address (SDO-ID)

Accessed

Device ID

Address range

Devices

0x2000

0x2000

– 0x27FF

Bus module

0x2800

0x2800

– 0x2FFF

FI 1

0x3000

0x3000

– 0x32FF

FI 2 (only SK xU4)

0x3800

0x3800

– 0x3FFF

FI 3 (only SK xU4)

0x4000

0x4000

– 0x43FF

FI 4 (only SK xU4)

Table 14: Device Assignment to SDO-ID

Information

SDO Handling

The handling of transmission or querying of SDOs depends on the PLC which is used. For B&R, SDOs can be
processed with the function blocks EplSDORead or EplSDOWrite. For detailed information, please contact the
manufacturer of the PLC.

Access to the parameter of the frequency inverter or the bus module is carried out by creating an
Index and a Sub-Index.