beautypg.com

Error monitoring via powerlink, Table 18: error entry structure, Information – NORD Drivesystems BU2200 User Manual

Page 34: 6 error monitoring and error messages, Fi-id

background image

6 Error monitoring and error messages

34

BU 2200 GB-3813

6.3.2 Error monitoring via POWERLINK

In case of FI malfunctions, the module generates an error entry in the object 0x1003
ERR_History_ADOM. In addition, errors are transmitted to the MN via the Emergency Queue, if the
MN supports this function.

For further information, please refer to the POWERLINK specification DS301.

The message is structured as follows.

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6 .. 13

Entry Type

Error code

Time stamp

FI ID (ASCii)

FI Error Code (ASCii)

Table 18: Error Entry Structure

Information

FI-ID

FI ID = identifies the FI from which the error message has come  FI1 = 1, FI2 = 2, etc. (for SK TU3-POL = 1)

Pos : 80 /Anl eitungen/ Elektroni k/ Bus s yst eme/6. M eldung en zum Betriebsz us tand / Fehler über wachung/ PO WER LINK [ BU 2200]/F ehl ergruppen @ 4\ mod_1378901501115_388. doc x @ 97541 @ 5 @ 1

Error Groups

The following error groups are defined in the communication profile DS-301. Because of the CAN over
... protocol which is used here, this profile also applies to the described Ethernet modules.

Error Code (hex)

Meaning

00xx

No error

10xx

Undefined error type

20xx

Current error

30xx

Voltage error

40xx

Temperature error

50xx

Hardware error

60xx

Software error

70xx

Additional module

80xx

communication

90xx

External error

FF00

Specific to device

Table 19: Error groups according to communication profile DS-301

Pos : 81 /Anl eitungen/ Elektroni k/ Bus s yst eme/6. M eldung en zum Betriebsz us tand / Fehler über wachung/ PO WER LINK [ BU 2200]/F ehl erlist e Bus fehler zu Umric ht erf ehl er @ 4\mod_1378901943404_388. doc x @ 97565 @ 5 @ 1