beautypg.com

Software version, P172 configuration level, Module status – NORD Drivesystems BU2200 User Manual

Page 27: Status of digital input

background image

POWERLINK Bus module

Supplementary manual options for NORD - Frequency Inverters

BU 2200 GB-3813

27

P171

... [-01]

... [-03]

Software Version

(Software Version/ Revision)

SK

EB…

SK TU3-

SK xU4-

16 bit

0 ... 9999

This parameter shows the software and revision numbers in the module. Array [-03] provides
information about any special versions of the hardware or software. A zero stands for the
standard version.

[-01] = Software version 1:

"Version number":

(E.g.: V1.0)

[-02] = Software version 2:

"Revision number":

(E.g.: R1)

[-03] = Software version 3:

"Special version":

(E.g.: 0)

Pos : 59 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/Bus übergreif end [ P150 ff. - P180 ff. ]/Par amet er P172

– Aus baus tufe [SK xU x- ..., SK EBIOE-2] @ 3\mod_1368786081911_388.doc x @ 69628 @ @ 1

P172

Configuration level

(Configuration level)

SK TU3-

SK xU4-

SK

EB…

16 bit

0 ... 4

Indicates the module version which is used.

0 =

CU4 (internal):

Internal module for decentralised frequency inverters

1 =

TU4 (external):

External module (IP55 / IP66)

2 =

TU3:

Bus module for FI series SK 5xxE

3=

TU3 (with DIP):

Module with DIP switches for FI series SK 5xxE

4=

EBIOE-2:

Decentralised module IP20

Pos : 60 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/Bus übergreif end [ P150 ff. - P180 ff. ]/Par amet er P173

– Baugruppenz us tand [SK xU x-..., SK EBIOE] @ 3\mod_1368792609372_388.doc x @ 69652 @ @ 1

P173

Module Status

(Module status)

SK

EB…

SK TU3-

SK xU4-

16 bit

0 ... 0xFFFF

Operating status of the module.

Bit 0 =

Module ready for operation*

Bit 1 =

Cyclic communication*

Bit 2 =

Timeout by Ethernet bus*

Bit 3 =

Timeout (P151/P513)*

Bit 4 =

No communication with ASIC*

Bit 5 =

General configuration error*

Bit 6 =

System bus "BUS Warning"**

Bit 7 =

System bus "BUS OFF"**

Bit 8 =

FI 1 status

Bit 9 =

FI 1 status

Bit 10 =

FI 2 status**

Bit 11 =

FI 2 status**

Bit 12 =

FI 3 status**

Bit 13 =

FI 3 status**

Bit 14 =

FI 4 status**

Bit 15 =

FI 4 status**

* Except for ...IOE modules

** Except for SK TU3 versions

THe status of the frequency inverter is determined from a High bit and a Low bit: e.g. FI
1: High bit: Bit 9; low Bit: Bit 8

High Bit

Low Bit

Meaning

0

0

FI is offline

0

1

FI is not supported

1

0

FI is online

1

1

Bus error (PDO or SDO monitoring)

Pos : 61 /Anl eitungen/ Elektroni k/ Par ameter/ P100-P199/ Buss pezi fisch/Bus übergreif end [ P150 ff. - P180 ff. ]/Par amet er P174

– Baugruppenz us tand [SK xU4-..., SK EBIOE] @ 3\mod_1369117740608_388.doc x @ 69680 @ @ 1

P174

Status of digital input

(Status of the digital inputs)

SK

EB…

SK xU4-

8 bit

0 ... 0xFF

Image of the switching status of the digital inputs of the module.