Example: "switch on and off + setpoint, Transfer of process data, Table 9: example: "switch fi on and off + setpoint – NORD Drivesystems BU2200 User Manual
Page 19: 3 transfer of process data
POWERLINK Bus module
–
Supplementary manual options for NORD - Frequency Inverters
BU 2200 GB-3813
19
4.2.5 Example: "Switch on and off + setpoint"
In this example, a frequency inverter is controlled with a setpoint (setpoint frequency). The frequency
inverter responds with an actual value (actual frequency). The "maximum frequency" is parameterised
to 50 Hz.
Relevant parameters:
Parameter
Setting value
Meaning
Parameter number
SK
180E …
SK 2xxE,
SK 54xE
SK
500E …
SK 535E
Maximum frequency
50.0
50 Hz
P105
P105
Actual bus value 1
1
Actual frequency
P543[-01]
P543
Function Bus setpoint 1
1
Setpoint frequency
P546[-01]
P546
Order to FI
Response from FI
Control word
Setpoint 1
Status word
Actual value
1
Explanation
- - -
- - -
0000h
0000h
- - -
- - -
xx40h
0000h
Switch-on of the mains voltage to the FI
047Eh
0000h
xx31h
0000h
Sets the FI in the status "Standby"
047Fh
2000h
xx37h
2000h
Sets the FI to the status "Operation
enabled" with the setpoint 50%.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 25 Hz.
0047Eh
2000h
xx31h
0000h
Sets the FI to "Standby" status. The
motor runs on its parameterised ramp up
to speed 0 and then the power is
switched off.
The FI is locked again and the motor is without current.
047Fh
1000h
xx37h
1000h
Sets the FI to the status "Operation
enabled" with the setpoint 25 %.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5 Hz.
Table 9: Example: "Switch FI on and off + setpoint"
Pos : 36 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /POWER LIN K [ BU 02200]/Pr oz ess datenübertrag ung [- PO L] @ 4\ mod_1378718695622_388. doc x @ 93 786 @ 2 @ 1
4.3 Transfer of process data
For POWERLINK the length and structure of the process data are fixed and are determined by the
XDD file. For each direction of transmission and inverter, 6 process values are always available. 1
control/status word and 5 setpoint/actual values. The SK 54xE FI series processes all 5 setpoint/actual
values. All other inverters only process 3 setpoint/actual values. The two other values are ignored.
In addition, for all SK xU4-POL, the switching status of the IOs of the bus module are communicated
via 2 further bytes.
Pos : 37 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /POWER LIN K [ BU 02200]/Mapping [- PO L] @ 4\ mod_1378733509396_388. doc x @ 93834 @ 5 @ 1