beautypg.com

Example: "switch on and off + setpoint, Transfer of process data, Table 9: example: "switch fi on and off + setpoint – NORD Drivesystems BU2200 User Manual

Page 19: 3 transfer of process data

background image

POWERLINK Bus module

Supplementary manual options for NORD - Frequency Inverters

BU 2200 GB-3813

19

4.2.5 Example: "Switch on and off + setpoint"

In this example, a frequency inverter is controlled with a setpoint (setpoint frequency). The frequency
inverter responds with an actual value (actual frequency). The "maximum frequency" is parameterised
to 50 Hz.

Relevant parameters:

Parameter

Setting value

Meaning

Parameter number

SK

180E …

SK 2xxE,
SK 54xE

SK

500E …

SK 535E

Maximum frequency

50.0

50 Hz

P105

P105

Actual bus value 1

1

Actual frequency

P543[-01]

P543

Function Bus setpoint 1

1

Setpoint frequency

P546[-01]

P546

Order to FI

Response from FI

Control word

Setpoint 1

Status word

Actual value

1

Explanation

- - -

- - -

0000h

0000h

- - -

- - -

xx40h

0000h

Switch-on of the mains voltage to the FI

047Eh

0000h

xx31h

0000h

Sets the FI in the status "Standby"

047Fh

2000h

xx37h

2000h

Sets the FI to the status "Operation
enabled" with the setpoint 50%.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 25 Hz.

0047Eh

2000h

xx31h

0000h

Sets the FI to "Standby" status. The
motor runs on its parameterised ramp up
to speed 0 and then the power is
switched off.

The FI is locked again and the motor is without current.

047Fh

1000h

xx37h

1000h

Sets the FI to the status "Operation
enabled" with the setpoint 25 %.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5 Hz.

Table 9: Example: "Switch FI on and off + setpoint"

Pos : 36 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /POWER LIN K [ BU 02200]/Pr oz ess datenübertrag ung [- PO L] @ 4\ mod_1378718695622_388. doc x @ 93 786 @ 2 @ 1

4.3 Transfer of process data

For POWERLINK the length and structure of the process data are fixed and are determined by the
XDD file. For each direction of transmission and inverter, 6 process values are always available. 1
control/status word and 5 setpoint/actual values. The SK 54xE FI series processes all 5 setpoint/actual
values. All other inverters only process 3 setpoint/actual values. The two other values are ignored.

In addition, for all SK xU4-POL, the switching status of the IOs of the bus module are communicated
via 2 further bytes.

Pos : 37 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /POWER LIN K [ BU 02200]/Mapping [- PO L] @ 4\ mod_1378733509396_388. doc x @ 93834 @ 5 @ 1