Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 98

DELTACHILL
™
Chillers
98
Chillers
Technical Manual : 7022932_V1.9_11/2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF026DX-08BKL0
6
270.4
69.6
256.2
75.8
240.8
82.7
224.3
90.4
7
278.7
70.0
264.1
76.2
248.3
83.1
231.3
90.8
8
287.1
70.4
272.1
76.6
255.9
83.5
238.4
91.2
10
304.3
71.2
288.4
77.4
271.3
84.3
252.9
92.1
12
321.9
72.1
305.2
78.3
287.3
85.2
267.9
93.0
14
340.1
73.0
322.5
79.2
303.6
86.2
283.3
94.0
DCF029DX-08BLL0
6
296.9
79.7
281.3
86.6
264.2
94.3
245.6
102.8
7
305.9
80.2
289.8
87.1
272.2
94.8
253.1
103.3
8
315.1
80.6
298.5
87.6
280.4
95.2
260.8
103.8
10
333.7
81.5
316.2
88.5
297.2
96.3
276.4
104.8
12
352.9
82.5
334.5
89.5
314.3
97.3
292.5
105.9
14
372.6
83.5
353.1
90.6
332.0
98.4
309.1
107.1
DCF032DX-08BLM0
6
321.0
87.3
303.5
94.8
284.5
103.2
264.0
112.5
7
330.5
87.9
312.5
95.4
293.0
103.8
271.9
113.1
8
340.3
88.4
321.8
96.1
301.7
104.5
280.0
113.8
10
360.1
89.6
340.5
97.3
319.3
105.8
296.5
115.1
12
380.4
90.9
359.8
98.6
337.4
107.1
313.4
116.6
14
401.2
92.2
379.5
100.0
356.0
108.5
330.7
118.0
DCF035DX-08BMM0
6
341.7
94.7
322.7
102.9
302.2
111.9
280.1
122.0
7
351.7
95.4
332.2
103.6
311.1
112.7
288.4
122.8
8
361.9
96.1
341.8
104.4
320.1
113.5
296.8
123.6
10
382.7
97.6
361.4
105.9
338.5
115.1
313.9
125.3
12
404.0
99.1
381.5
107.5
357.3
116.8
331.4
127.0
14
425.7
100.6
402.0
109.2
376.6
118.5
349.4
128.8
DCF039DX-10BMS0
6
395.8
107.4
374.2
116.7
350.8
127.0
325.5
138.4
7
407.6
108.1
385.5
117.4
361.4
127.7
335.4
139.2
8
419.7
108.8
396.9
118.2
372.1
128.5
345.4
140.0
10
444.2
110.3
420.1
119.7
394.0
130.1
365.8
141.6
12
469.4
111.8
444.0
121.3
416.4
131.7
386.8
143.3
14
495.2
113.3
468.4
122.9
439.4
133.4
408.3
145.1
DCF044DX-12BSS0
6
444.6
119.8
421.1
130.2
395.4
141.7
367.4
154.5
7
458.1
120.5
433.9
130.9
407.5
142.4
378.7
155.2
8
471.8
121.2
446.9
131.6
419.8
143.2
390.2
156.0
10
499.8
122.5
473.5
133.0
444.8
144.7
413.7
157.6
12
528.6
124.0
500.8
134.5
470.6
146.3
437.8
159.2
14
558.1
125.5
528.8
136.1
497.0
147.9
462.6
160.9
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.