Chillers deltachill, Chillers, Cooling performance ec fans extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 41

Chillers
DELTACHILL
™
Chillers
41
Technical Manual :7022932_V1.9_11/2013
Cooling Performance EC Fans Extra Quiet
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC036DX-08BMS0
5
377.8
102.5
356.9
111.9
334.4
122.1
310.4
133.3
6
389.2
103.2
367.7
112.6
344.6
122.9
319.9
134.1
7
400.8
103.9
378.6
113.4
354.9
123.6
329.6
134.9
8
412.5
104.7
389.7
114.1
365.3
124.4
339.3
135.7
9
424.3
105.4
400.9
114.9
375.9
125.2
349.2
136.5
10
436.3
106.2
412.3
115.7
386.7
126.1
359.3
137.4
DCC038DX-10BMS0
5
389.1
98.6
368.7
107.6
346.8
117.5
323.3
128.3
6
401.1
99.1
380.2
108.2
357.6
118.1
333.5
128.9
7
413.3
99.7
391.8
108.8
368.6
118.7
343.8
129.6
8
425.6
100.3
403.6
109.4
379.8
119.3
354.3
130.2
9
438.2
100.9
415.5
110.0
391.1
120.0
364.9
130.9
10
450.9
101.5
427.6
110.7
402.6
120.6
375.7
131.6
DCC039DX-08BSS0
5
413.4
117.7
389.9
128.5
364.8
140.3
337.8
153.2
6
425.7
118.6
401.6
129.4
375.7
141.2
348.0
154.1
7
438.2
119.4
413.4
130.2
386.9
142.1
358.4
155.1
8
450.9
120.3
425.4
131.1
398.1
143.0
368.9
156.0
9
463.7
121.1
437.6
132.0
409.6
143.9
379.6
156.9
10
476.7
122.0
449.9
133.0
421.1
144.9
390.4
157.9
DCC042DX-12BSS0
5
435.9
109.8
413.7
119.9
389.6
131.0
363.6
143.2
6
449.5
110.4
426.6
120.5
401.8
131.6
375.1
143.8
7
463.2
110.9
439.8
121.1
414.3
132.2
386.9
144.4
8
477.2
111.5
453.1
121.7
427.0
132.8
398.8
145.1
9
491.4
112.1
466.7
122.3
439.9
133.4
411.0
145.7
10
505.9
112.7
480.5
122.9
453.0
134.1
423.3
146.3
DCC043DX-08BST0
5
443.1
131.1
417.0
142.9
389.1
155.9
359.3
170.2
6
456.1
132.1
429.2
144.0
400.5
157.0
369.9
171.3
7
469.3
133.2
441.6
145.1
412.1
158.2
380.7
172.5
8
482.6
134.3
454.2
146.3
423.9
159.4
391.7
173.7
9
496.0
135.5
466.9
147.4
435.8
160.5
402.7
174.9
10
509.6
136.6
479.7
148.6
447.8
161.8
413.9
176.1
DCC045DX-12BST0
5
470.8
121.1
445.8
132.3
418.9
144.4
390.1
157.8
6
485.2
121.9
459.5
133.0
431.9
145.2
402.4
158.5
7
499.9
122.6
473.5
133.8
445.2
146.0
414.8
159.4
8
514.8
123.3
487.7
134.5
458.6
146.8
427.4
160.2
9
530.0
124.1
502.1
135.3
472.2
147.6
440.2
161.0
10
545.4
124.9
516.8
136.1
486.1
148.4
453.2
161.9
DCC046DX-10BTT0
5
487.7
136.7
460.0
149.1
430.5
162.7
399.0
177.7
6
502.2
137.8
473.7
150.2
443.4
163.8
411.0
178.8
7
516.9
138.8
487.6
151.3
456.4
165.0
423.2
180.0
8
531.8
139.9
501.7
152.5
469.6
166.1
435.5
181.2
9
546.9
141.0
516.0
153.6
483.0
167.3
448.0
182.4
10
562.2
142.1
530.4
154.8
496.6
168.5
460.7
183.6
DCC048DX-12BTT0
5
500.5
132.2
473.3
144.4
444.2
157.6
413.2
172.1
6
515.6
133.1
487.7
145.3
457.8
158.5
425.9
173.1
7
531.1
134.0
502.3
146.2
471.6
159.5
438.8
174.1
8
546.7
134.9
517.2
147.2
485.6
160.5
451.9
175.1
9
562.6
135.9
532.2
148.2
499.8
161.5
465.2
176.1
10
578.7
136.8
547.5
149.1
514.2
162.5
478.7
177.1
DCC051DX-10BVV0
5
537.8
157.2
505.9
174.3
472.4
193.4
436.8
214.9
6
553.3
158.4
520.5
175.6
486.1
194.8
449.6
216.4
7
568.9
159.7
535.4
176.9
500.0
196.2
462.5
217.8
8
584.9
161.0
550.4
178.3
514.1
197.7
475.7
219.3
9
601.0
162.4
565.7
179.7
528.5
199.1
489.0
220.8
10
617.3
163.7
581.1
181.1
543.0
200.6
502.6
222.4
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.