Positioning, Deltachill ™ chillers, Installation data – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 152

DELTACHILL
™
Chillers
152
Chillers
Technical Manual : 7022932_V1.9_11/2013
Installation Data
Positioning
The installation position should be selected with the following points in mind:
Position on a stable and even base, levelled to ensure that the compressor
operates correctly
Levelling should be to +/- 5mm
Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections
Observe airflow and maintenance clearances
Pipework and electrical connections are readily accessible
Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity
Within a side enclosed installation, the fan MUST be higher than the
enclosing structure
Increase airflow and maintenance clearances for side-enclosed or multiple
unit applications
Allow free space above the fans to prevent air recirculation
Ensure that there is a safe access and operating area provided for unit controls.
CAUTION
Prior to connecting services, ensure that the equipment is installed and
completely level.
Airflow & Maintenance
Clearances
A
A
B
C
D
Application
Distance from Overall Base Dimension (mm)
A
B
C
D
Free of walls and overhang
1300
1300
1300
1300
Enclosed to A
2600
1300
1300
1300
Unit parallel with A
2600
1300
1300
1300
Enclosed to B
1300
2600
1300
1300
Unit in line with B
1300
1300
1300
1300
Unit in line with C Controls End
1300
1300
2600
1300
Enclosed to C
1300
1300
2600
1300