Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 104

DELTACHILL
™
Chillers
104
Chillers
Technical Manual : 7022932_V1.9_11/2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF026DX-08BKL0
6
267.7
66.2
253.3
72.5
237.7
79.5
221.0
87.4
7
275.8
66.6
261.0
72.9
245.0
80.0
227.8
87.9
8
284.1
67.1
268.9
73.4
252.4
80.4
234.8
88.3
10
300.9
67.9
284.9
74.3
267.6
81.4
248.9
89.3
12
318.2
68.9
301.3
75.2
283.1
82.3
263.5
90.3
14
335.9
69.9
318.1
76.2
299.0
83.3
278.5
91.3
DCF029DX-08BLL0
6
293.7
76.6
277.8
83.6
260.4
91.4
241.5
100.1
7
302.5
77.1
286.1
84.1
268.3
92.0
248.8
100.6
8
311.4
77.6
294.6
84.7
276.2
92.5
256.3
101.2
10
329.7
78.6
311.9
85.7
292.5
93.6
271.5
102.4
12
348.4
79.6
329.6
86.8
309.2
94.8
287.1
103.6
14
367.6
80.7
347.8
88.0
326.3
96.0
303.1
104.8
DCF032DX-08BLM0
6
316.9
84.5
299.2
92.1
279.9
100.7
259.1
110.1
7
326.3
85.1
308.0
92.8
288.2
101.4
266.8
110.9
8
335.8
85.7
317.0
93.5
296.6
102.1
274.6
111.6
10
355.1
87.0
335.2
94.9
313.7
103.5
290.6
113.1
12
374.9
88.4
353.9
96.3
331.2
105.0
306.9
114.6
14
395.1
89.8
373.0
97.8
349.2
106.5
323.6
116.2
DCF035DX-08BMM0
6
337.0
92.1
317.7
100.5
296.9
109.7
274.6
120.0
7
346.8
92.9
326.9
101.3
305.6
110.6
282.5
120.9
8
356.7
93.7
336.3
102.1
314.3
111.4
290.6
121.8
10
376.9
95.3
355.3
103.8
332.0
113.2
307.1
123.6
12
397.6
96.9
374.7
105.5
350.2
115.0
324.0
125.4
14
418.6
98.6
394.5
107.3
368.7
116.9
341.2
127.4
DCF039DX-10BMS0
6
390.9
103.8
369.0
113.3
345.3
123.8
319.6
135.4
7
402.5
104.6
379.9
114.1
355.5
124.6
329.2
136.3
8
414.2
105.3
391.0
114.9
365.9
125.4
338.8
137.1
10
438.2
106.9
413.7
116.5
387.2
127.2
358.6
138.9
12
462.7
108.6
436.8
118.3
408.9
129.0
378.8
140.8
14
487.7
110.2
460.5
120.0
431.1
130.8
399.6
142.7
DCF044DX-12BSS0
6
439.7
115.1
415.8
125.7
389.7
137.4
361.4
150.4
7
452.9
115.9
428.3
126.5
401.5
138.2
372.4
151.3
8
466.4
116.6
441.1
127.2
413.5
139.0
383.5
152.1
10
493.7
118.1
467.0
128.8
437.9
140.7
406.3
153.9
12
521.8
119.7
493.6
130.5
462.9
142.4
429.7
155.7
14
550.6
121.3
520.8
132.2
488.5
144.2
453.6
157.5
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.