Deltachill free cool, Cooling performance free cool, Deltachill ™ chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 90

DELTACHILL
™
Chillers
90
Chillers
Technical Manual : 7022932_V1.9_11/2013
DeltaChill Free Cool
Cooling Performance Free Cool
The Freecool potential of the DeltaChill can be determined by the temperature difference of the ambient air and the
return water temperatures. The graphs show a temperature difference and therefore changing Freecool ability.
The cooling capacity is derived by multiplying the total number of fans on the unit by the values of flowrate and capacity.
Example
Return water temperature 15°C
Temperature difference from ambient to return water temperature 10°C
Therefore ambient 5°C
DCF014SR-04AL00 chiller having 4 fans equates to
Cooling capacity
35kW x 4
=
140kW*
Flowrate
2 l/s x 4
=
8 l/s*
*Exact cooling capacity and water flowrate may change for unit given above.