Chillers deltachill, Chillers, Electrical data regular quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 71

Chillers
DELTACHILL
™
Chillers
71
Technical Manual :7022932_V1.9_11/2013
Electrical Data Regular Quiet Continued
ELECTRICAL DATA
DCC031DR-08BLM0
DCC032DR-06BMM0
DCC033DR-08BMM0
Unit Data
Nominal Run Amps
(1)
A
215.5
215.8
224.4
Maximum Start Amps
(2)
A
488.0
488.3
496.9
Recommended Mains Fuse Size
A
250
250
250
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
8
6
8
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
8
6
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 43.1
47.5 / 47.5
47.5 / 47.5
Quantity
2 + 2
2 + 2
2 + 2
Motor Rating
kW
28.2 / 24.0
28.2 / 28.2
28.2 / 28.2
Sump Heater Rating
W
130 + 75
130
130
Start Amps (2)
A
320 / 260
320 / 260
320 / 320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
42.8
42.8
Circuit 2 Comp RLA (PFC)
36.5
42.8
42.8
Nominal Run Amps
A
192.9
196.9
205.5
Maximum Start Amps
A
470.2
414.2
482.8
Compressor Nominal Run Amps
A
42.8 / 36.5
42.8 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
250
Electronic Soft-start
Nominal Run Amps
A
215.5
215.8
224.4
Maximum Start Amps
A
360.0
360.3
368.9
Recommended Mains Fuse
A
250
250
250
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
192.9
196.9
205.5
Maximum Start Amps
A
342.2
310.2
354.8
Compressor Nominal Run Amps
A
42.8 / 36.5
42.8 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
250
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.2
8.9
8.9
Unit Nominal Run Amps
A
221.7
224.66
233.26
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
3
4
4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
12
12
Unit Nominal Run Amps
A
224.4
227.76
236.36
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
4
5.5
5.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
226.7
227.0
235.6
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
226.7
226.96
235.56
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.