Technical Manual : 7022932_V1.9_11/2013
Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC015DX-04ADF0
DCC016DX-04AJJ0
DCC018DX-04BJK0
Unit Data
Nominal Run Amps
(1)
A
100.6
118.0
135.0
Maximum Start Amps
(2)
A
373.1
271.0
317.0
Recommended Mains Fuse Size
A
125
160
160
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
6
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
4
4
6
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 43.1
27.0 / 27.0
33.0 / 27.0
Quantity
1 + 1
2 + 2
2 + 2
Motor Rating
kW
28.2 / 24.0
13.7 / 13.7
18.8 / 13.7
Sump Heater Rating
W
130 + 75
75
75
Start Amps (2)
A
320 / 260
180 / 180
215 / 180
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
20.9
28.5
Circuit 2 Comp RLA (PFC)
36.5
20.9
20.9
Nominal Run Amps
A
89.3
93.4
113.7
Maximum Start Amps
A
366.5
252.6
300.2
Compressor Nominal Run Amps
A
42.8 / 36.5
20.9 / 20.9
28.5 / 20.9
Recommended Mains Fuse Size
A
125
160
160
Electronic Soft-start
Nominal Run Amps
A
100.55
118
135.04
Maximum Start Amps
A
245.06
199
231.02
Recommended Mains Fuse
A
125
160
160
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
89.3
93.4
113.7
Maximum Start Amps
A
238.5
180.6
214.2
Compressor Nominal Run Amps
A
42.8 / 36.5
20.9 / 20.9
28.5 / 20.9
Recommended Mains Fuse Size
A
125
160
160
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
105.6
123.0
140.0
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
2.2
2.2
2.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
6.6
6.6
Unit Nominal Run Amps
A
105.6
124.6
141.6
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
2.2
3
3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
4.5
4.5
4.5
Unit Nominal Run Amps
A
105.0
122.5
139.5
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
2.2
2.2
2.2
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
6.3
Unit Nominal Run Amps
A
106.9
124.3
141.3
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
3
3
3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.