Deltachill ™ chillers, Chillers, Electrical data regular quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 74

DELTACHILL
™
Chillers
74
Chillers
Technical Manual : 7022932_V1.9_11/2013
Electrical Data Regular Quiet Continued
ELECTRICAL DATA
DCC046DR-08BTT0
DCC048DR-10BTT0
DCC051DR-08BVV0
Unit Data
Nominal Run Amps
(1)
A
319.3
327.9
365.6
Maximum Start Amps
(2)
A
591.9
600.5
577.4
Recommended Mains Fuse Size
A
355
355
400
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
17
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
8
10
8
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
8
10
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5
47.5 / 47.5
55.2 / 55.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
28.2 / 28.2
28.2 / 28.2
33.1 / 33.1
Sump Heater Rating
W
130
130
140
Start Amps (2)
A
320 / 320
320 / 320
267 / 267
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
42.8
50.3
Circuit 2 Comp RLA (PFC)
42.8
42.8
50.3
Nominal Run Amps
A
291.1
299.7
336.1
Maximum Start Amps
A
568.3
576.9
552.9
Compressor Nominal Run Amps
A
42.8 / 42.8
42.8 / 42.8
50.3 / 50.3
Recommended Mains Fuse Size
A
355
355
400
Electronic Soft-start
Nominal Run Amps
A
319.34
327.94
365.6
Maximum Start Amps
A
463.85
472.45
470.6
Recommended Mains Fuse
A
355
355
400
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
291.1
299.7
336.1
Maximum Start Amps
A
440.3
448.9
446.1
Compressor Nominal Run Amps
A
42.8 / 42.8
42.8 / 42.8
50.3 / 50.3
Recommended Mains Fuse Size
A
355
355
400
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
12
12
12
Unit Nominal Run Amps
A
331.34
339.94
377.6
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
5.5
5.5
5.5
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14
14
14
Unit Nominal Run Amps
A
333.3
341.9
379.6
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
7.5
7.5
7.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
330.5
339.1
376.8
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
5.5
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
14.8
Unit Nominal Run Amps
A
334.1
342.7
380.4
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
7.5
7.5
7.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.