Electrical Data Free Cool Chiller Regular Quiet Continued
ELECTRICAL DATA
DCF025SR-06BT00
DCF013DR-04ACD0
DCF014DR-04ADD0
Unit Data
Nominal Run Amps
(1)
A
169.5
94.1
104.1
Maximum Start Amps
A
442.0
321.1
321.1
Recommended Mains Fuse Size
A
200
125
125
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
6
4
4
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
6
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
47.5
33.0 / 43.1
43.1 / 43.1
Quantity
3
1 + 1
1 + 1
Motor Rating
kW
28.2
18.8 / 24.0
24.0 / 24.0
Sump Heater Rating
W
130
75
75
Start Amps
A
320
215 / 260
260 / 260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
28.5
36.5
Circuit 2 Comp RLA (PFC)
N/A
36.5
36.5
Nominal Run Amps
A
155.4
83.0
91.0
Maximum Start Amps
A
432.6
314.5
314.5
Compressor Nominal Run Amps
A
42.8
28.5 / 36.5
36.5 / 36.5
Recommended Mains Fuse Size
A
200
125
125
Electronic Soft-start
Nominal Run Amps
A
169.5
94.1
104.1
Maximum Start Amps
A
314.0
207.0
217.1
Recommended Mains Fuse
A
200.0
125.0
125.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
155.4
83.0
91.0
Maximum Start Amps
A
304.6
202.5
210.5
Compressor Nominal Run Amps
A
42.8
28.5 / 36.5
36.5 / 36.5
Recommended Mains Fuse Size
A
200
125
125
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
6
4
4
Full Load Amps
A
4.5
4.5
4.5
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
2.86
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
12
6.6
6.6
Unit Nominal Run Amps
A
181.5
100.7
110.7
Recommended Mains Fuse Size
A
200
125
125
Motor Rating
kW
5.5
3
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.8
9.8
9.8
Unit Nominal Run Amps
A
181.3
103.9
113.9
Recommended Mains Fuse Size
A
200
125
125
Motor Rating
kW
5.5
4
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
6.3
6.3
Unit Nominal Run Amps
A
180.7
100.4
110.4
Recommended Mains Fuse Size
A
200
125
125
Motor Rating
kW
5.5
3
3
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
8
8
Unit Nominal Run Amps
A
184.3
102.1
112.1
Recommended Mains Fuse Size
A
200
125
125
Motor Rating
kW
7.5
4
4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.