Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 101

Chillers
DELTACHILL
™
Chillers
101
Technical Manual :7022932_V1.9_11/2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF026DR-06BKL0
6
264.1
70.1
250.7
76.8
236.5
84.2
221.4
92.6
7
272.3
70.6
258.5
77.3
244.0
84.8
228.6
93.1
8
280.6
71.1
266.5
77.8
251.6
85.3
235.7
93.6
10
297.5
72.2
282.9
78.9
267.3
86.4
250.3
94.6
12
315.1
73.3
299.8
80.0
283.5
87.6
265.2
95.6
14
333.2
74.5
317.1
81.2
300.0
88.7
280.7
96.7
DCF029DR-06BLL0
6
291.2
81.4
276.6
88.8
261.0
97.0
244.3
106.2
7
300.2
81.9
285.2
89.4
269.2
97.6
252.2
106.8
8
309.3
82.5
293.9
90.0
277.6
98.3
259.9
107.4
10
328.1
83.7
312.0
91.2
294.8
99.6
275.6
108.5
12
347.4
85.0
330.5
92.5
312.6
100.9
291.6
109.6
14
367.3
86.3
349.7
93.8
330.7
102.1
308.1
110.7
DCF032DR-08BLM0
6
323.5
84.8
307.3
92.6
290.0
101.2
271.4
110.8
7
333.5
85.4
316.9
93.2
299.1
101.8
280.1
111.4
8
343.7
86.0
326.6
93.8
308.4
102.5
288.9
112.1
10
364.5
87.3
346.6
95.2
327.4
103.8
307.0
113.5
12
386.1
88.6
367.2
96.5
347.1
105.2
325.7
115.0
14
408.2
89.9
388.8
98.0
367.4
106.7
345.0
116.4
DCF035DR-08BMM0
6
346.1
92.4
328.6
100.8
310.0
110.1
290.3
120.5
7
356.7
93.1
338.7
101.6
319.6
110.9
299.5
121.3
8
367.5
93.9
349.0
102.3
329.5
111.7
308.7
122.1
10
389.7
95.4
370.2
103.9
349.7
113.3
327.9
123.8
12
412.5
96.9
392.1
105.5
370.5
115.0
347.7
125.5
14
436.1
98.5
414.6
107.1
392.1
116.7
368.3
127.2
DCF039DR-10BMS0
6
398.6
104.4
378.6
114.0
357.2
124.6
334.3
136.4
7
411.0
105.1
390.5
114.8
368.5
125.4
345.0
137.3
8
423.6
105.9
402.5
115.6
379.9
126.2
355.9
138.1
10
449.4
107.4
427.2
117.1
403.5
127.9
378.2
139.8
12
476.0
109.0
452.7
118.8
427.8
129.5
401.4
141.5
14
503.4
110.6
478.9
120.4
452.9
131.3
425.3
143.3
DCF044DR-10BSS0
6
439.6
119.7
417.6
130.7
393.9
142.9
368.7
156.5
7
453.2
120.5
430.7
131.6
406.4
143.8
380.5
157.4
8
467.1
121.4
443.9
132.4
419.1
144.7
392.6
158.3
10
495.5
123.1
471.1
134.2
445.1
146.5
417.3
160.2
12
524.8
124.8
499.3
136.0
472.0
148.4
443.0
162.2
14
555.0
126.6
528.2
137.8
499.8
150.3
469.5
164.1
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.