Chillers deltachill, Chillers, Electrical data regular quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 65

Chillers
DELTACHILL
™
Chillers
65
Technical Manual :7022932_V1.9_11/2013
Electrical Data Regular Quiet Continued
ELECTRICAL DATA
DCC021SR-04BS00
DCC023SR-04BT00
DCC024SR-06BT00
Unit Data
Nominal Run Amps
(1)
A
146.4
159.7
168.3
Maximum Start Amps
(2)
A
363.3
432.2
440.8
Recommended Mains Fuse Size
A
160
200
200
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
6
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
4
4
6
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1
47.5
47.5
Quantity
3
3
3
Motor Rating
kW
24.0
28.2
28.2
Sump Heater Rating
W
75
130
130
Start Amps (2)
A
260
320
320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
42.8
42.8
Circuit 2 Comp RLA (PFC)
N/A
N/A
N/A
Nominal Run Amps
A
126.7
145.6
154.2
Maximum Start Amps
A
350.2
422.8
431.4
Compressor Nominal Run Amps
A
36.5
42.8
42.8
Recommended Mains Fuse Size
A
160
200
200
Electronic Soft-start
Nominal Run Amps
A
146.4
159.7
168.3
Maximum Start Amps
A
259.3
304.2
312.8
Recommended Mains Fuse
A
160
200
200
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
126.7
145.6
154.2
Maximum Start Amps
A
246.2
294.8
303.4
Compressor Nominal Run Amps
A
36.5
42.8
42.8
Recommended Mains Fuse Size
A
160
200
200
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
6.2
6.2
Unit Nominal Run Amps
A
151.4
165.9
174.5
Recommended Mains Fuse Size
A
200
200
200
Motor Rating
kW
2.2
3
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.6
8.9
8.9
Unit Nominal Run Amps
A
153.0
168.6
177.2
Recommended Mains Fuse Size
A
200
200
200
Motor Rating
kW
3
4
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
4.5
6.3
8.0
Unit Nominal Run Amps
A
150.8
166.0
176.3
Recommended Mains Fuse Size
A
200
200
200
Motor Rating
kW
2.2
3
4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
8
8
Unit Nominal Run Amps
A
152.7
167.7
176.3
Recommended Mains Fuse Size
A
200
200
200
Motor Rating
kW
3
4
4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.