Cooling performance ac fans extra quiet, Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 30

DELTACHILL
™
Chillers
30
Chillers
Technical Manual : 7022932_V1.9_11/2013
Cooling Performance AC Fans Extra Quiet
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC011SX-04AK00
5
117.3
28.3
111.4
31.0
105.3
33.9
98.8
37.2
6
121.0
28.4
115.0
31.1
108.7
34.0
102.0
37.3
7
124.8
28.5
118.7
31.2
112.2
34.1
105.3
37.4
8
128.7
28.7
122.4
31.3
115.7
34.3
108.7
37.5
9
132.7
28.8
126.2
31.4
119.3
34.4
112.1
37.7
10
136.7
29.0
130.0
31.6
123.0
34.5
115.6
37.8
DCC014SX-04AL00
5
147.0
37.8
139.7
41.1
131.9
44.7
123.4
48.7
6
151.6
38.0
144.2
41.3
136.1
44.9
127.4
48.9
7
156.3
38.1
148.7
41.4
140.4
45.1
131.4
49.0
8
161.1
38.3
153.3
41.6
144.7
45.2
135.5
49.2
9
166.0
38.5
157.9
41.8
149.2
45.4
139.7
49.4
10
170.9
38.6
162.7
42.0
153.7
45.6
144.0
49.6
DCC017SX-04AM00
5
171.0
44.4
162.2
48.4
152.7
52.6
142.6
57.3
6
176.3
44.7
167.2
48.6
157.5
52.9
147.1
57.6
7
181.6
45.0
172.3
48.9
162.3
53.2
151.6
57.9
8
187.1
45.2
177.5
49.2
167.2
53.5
156.2
58.2
9
192.6
45.5
182.8
49.5
172.2
53.8
160.9
58.5
10
198.2
45.8
188.1
49.8
177.3
54.1
165.7
58.8
DCC021SX-06BS00
5
220.4
56.8
209.5
61.8
197.7
67.2
184.9
73.2
6
227.3
57.1
216.1
62.0
204.0
67.5
190.8
73.5
7
234.4
57.3
222.9
62.3
210.4
67.7
196.9
73.7
8
241.5
57.6
229.7
62.5
216.9
68.0
203.0
74.0
9
248.8
57.8
236.7
62.8
223.5
68.3
209.2
74.3
10
256.2
58.1
243.7
63.1
230.2
68.5
215.6
74.6
DCC023SX-04BT00
5
241.4
71.7
227.3
78.0
212.3
84.9
196.4
92.5
6
248.5
72.3
234.0
78.6
218.6
85.5
202.2
93.1
7
255.7
72.9
240.8
79.2
224.9
86.1
208.0
93.8
8
262.9
73.5
247.6
79.8
231.3
86.8
214.0
94.4
9
270.3
74.1
254.5
80.5
237.8
87.4
220.1
95.1
10
277.7
74.7
261.5
81.1
244.4
88.1
226.2
95.7
DCC024SX-06BT00
5
255.8
67.6
242.2
73.6
227.7
80.1
212.3
87.2
6
263.7
68.0
249.7
74.0
234.8
80.5
218.9
87.6
7
271.6
68.4
257.3
74.4
242.0
80.9
225.6
88.1
8
279.8
68.9
265.0
74.9
249.3
81.4
232.5
88.5
9
288.0
69.3
272.9
75.3
256.7
81.8
239.4
89.0
10
296.3
69.7
280.8
75.8
264.2
82.3
246.5
89.5
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.