Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 94

DELTACHILL
™
Chillers
94
Chillers
Technical Manual : 7022932_V1.9_11/2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF013DR-04ACD0
6
137.7
35.5
131.0
38.5
123.8
42.0
116.0
45.8
7
142.1
35.6
135.2
38.7
127.8
42.1
119.7
45.9
8
146.5
35.8
139.4
38.9
131.9
42.3
123.5
46.1
10
155.6
36.2
148.1
39.3
140.2
42.7
131.3
46.5
12
164.9
36.7
157.1
39.7
148.7
43.1
139.2
46.8
14
174.6
37.1
166.4
40.2
157.4
43.5
147.4
47.2
DCF014DR-04ADD0
6
152.6
40.5
145.0
43.9
136.7
47.5
127.7
51.6
7
157.3
40.7
149.5
44.0
141.0
47.7
131.7
51.8
8
162.1
40.9
154.1
44.2
145.3
47.9
135.8
52.0
10
172.0
41.3
163.5
44.6
154.2
48.3
144.2
52.4
12
182.1
41.7
173.2
45.0
163.4
48.7
152.8
52.8
14
192.5
42.1
183.1
45.5
172.9
49.2
161.7
53.3
DCF015DR-04ADF0
6
165.6
44.2
157.0
47.9
147.7
51.9
137.7
56.3
7
170.7
44.5
161.9
48.1
152.3
52.1
142.0
56.6
8
175.9
44.7
166.8
48.4
156.9
52.4
146.3
56.9
10
186.4
45.2
176.8
48.9
166.4
52.9
155.2
57.4
12
197.2
45.7
187.1
49.4
176.2
53.5
164.4
58.0
14
208.4
46.3
197.7
50.0
186.2
54.1
173.8
58.6
DCF016DR-04AJJ0
6
171.8
46.1
162.6
50.0
152.8
54.5
142.3
59.4
7
177.2
46.3
167.7
50.3
157.7
54.7
146.9
59.7
8
182.7
46.5
173.0
50.5
162.6
55.0
151.6
59.9
10
193.9
47.1
183.6
51.1
172.7
55.5
161.0
60.5
12
205.4
47.6
194.6
51.7
183.1
56.1
170.8
61.1
14
217.2
48.2
205.8
52.2
193.3
56.8
180.8
61.8
DCF018DR-04BJK0
6
198.0
55.0
187.0
60.0
175.3
65.6
162.7
71.9
7
204.0
55.3
192.6
60.4
180.6
66.0
167.8
72.3
8
210.0
55.7
198.4
60.8
186.1
66.4
172.9
72.7
10
222.4
56.5
210.2
61.6
197.1
67.2
183.2
73.5
12
235.1
57.3
222.2
62.4
208.5
68.1
193.9
74.4
14
248.1
58.2
234.5
63.3
220.2
69.0
204.8
75.3
DCF020DR-06BFK0
6
209.3
54.2
198.8
59.1
187.7
64.4
176.0
70.5
7
215.9
54.6
205.1
59.4
193.7
64.8
181.6
70.7
8
222.5
54.9
211.5
59.7
199.8
65.1
187.2
71.0
10
236.2
55.6
224.5
60.4
212.3
65.8
198.8
71.7
12
250.2
56.3
238.0
61.1
225.1
66.5
210.7
72.3
14
264.8
57.0
252.0
61.8
238.1
67.1
223.0
73.0
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.