Deltachill ™ chillers, Chillers, Mechanical cooling ec fans regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 100

DELTACHILL
™
Chillers
100
Chillers
Technical Manual : 7022932_V1.9_11/2013
Mechanical Cooling EC Fans Regular Quiet
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF013DR-04ACD0
6
135.6
33.1
128.9
36.3
121.7
39.8
114.0
43.8
7
139.8
33.3
132.9
36.5
125.6
40.1
117.7
44.1
8
144.1
33.5
137.1
36.7
129.5
40.3
121.5
44.3
10
153.0
34.0
145.6
37.2
137.7
40.8
129.2
44.8
12
162.2
34.5
154.4
37.7
146.1
41.3
137.2
45.3
14
171.6
35.0
163.4
38.2
154.8
41.8
145.5
45.8
DCF014DR-04ADD0
6
149.7
38.3
142.4
41.9
134.5
45.8
125.9
50.2
7
154.3
38.6
146.9
42.1
138.8
46.1
130.0
50.5
8
159.1
38.8
151.4
42.4
143.1
46.3
134.2
50.7
10
168.9
39.3
160.8
42.9
152.1
46.9
142.7
51.3
12
179.0
39.8
170.5
43.4
161.3
47.4
151.5
51.9
14
189.3
40.4
180.4
44.0
170.9
48.0
160.5
52.4
DCF015DR-04ADF0
6
163.0
42.4
154.8
46.3
146.1
50.6
136.7
55.4
7
168.1
42.7
159.7
46.6
150.7
50.9
141.1
55.7
8
173.2
43.0
164.6
46.9
155.4
51.3
145.6
56.1
10
183.8
43.7
174.7
47.6
165.0
52.0
154.7
56.8
12
194.7
44.3
185.2
48.3
175.0
52.7
164.2
57.5
14
206.0
45.0
196.1
49.0
185.3
53.4
174.0
58.3
DCF016DR-04AJJ0
6
169.4
44.6
160.7
48.8
151.5
53.5
141.9
58.8
7
174.8
44.9
165.9
49.1
156.5
53.8
146.6
59.2
8
180.3
45.2
171.2
49.4
161.6
54.2
151.4
59.5
10
191.6
45.8
182.0
50.1
171.9
54.9
161.3
60.2
12
203.3
46.5
193.2
50.8
182.6
55.6
171.5
61.0
14
215.3
47.2
204.7
51.5
193.6
56.4
182.0
61.7
DCF018DR-04BJK0
6
197.8
54.3
187.4
59.5
176.1
65.1
164.1
71.5
7
203.9
54.7
193.2
59.9
181.6
65.5
169.3
71.9
8
210.2
55.1
199.0
60.3
187.1
66.0
174.5
72.3
10
222.9
56.0
211.0
61.1
198.5
66.8
185.3
73.2
12
235.8
56.8
223.4
62.0
210.3
67.7
196.3
74.1
14
249.1
57.7
236.0
62.9
222.3
68.6
207.7
75.0
DCF020DR-06BFK0
6
206.2
50.9
195.9
55.9
184.9
61.5
173.2
67.7
7
212.6
51.3
202.0
56.3
190.8
61.9
178.8
68.1
8
219.1
51.6
208.3
56.7
196.7
62.2
184.4
68.5
10
232.5
52.4
221.1
57.4
208.9
63.0
196.1
69.3
12
246.2
53.2
234.3
58.2
221.6
63.8
208.1
70.1
14
260.4
54.0
247.9
59.1
234.6
64.7
220.5
70.9
DCF023DR-06BKK0
6
231.9
58.5
220.1
64.5
207.8
71.1
194.7
78.7
7
239.0
58.9
227.0
64.9
214.3
71.6
201.0
79.1
8
246.3
59.4
234.0
65.3
221.0
72.0
207.4
79.5
10
261.2
60.3
248.3
66.2
234.8
72.9
220.5
80.4
12
276.5
61.2
263.2
67.2
249.0
73.9
234.0
81.4
14
292.4
62.2
278.4
68.2
263.6
74.8
248.0
82.4
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.