Chillers deltachill, Chillers, Electrical data regular quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 73

Chillers
DELTACHILL
™
Chillers
73
Technical Manual :7022932_V1.9_11/2013
Electrical Data Regular Quiet Continued
ELECTRICAL DATA
DCC042DR-10BSS0
DCC043DR-08BST0
DCC045DR-10BST0
Unit Data
Nominal Run Amps
(1)
A
301.4
306.1
314.7
Maximum Start Amps
(2)
A
518.3
578.6
587.2
Recommended Mains Fuse Size
A
315
355
355
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
10
8
10
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
10
8
10
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1 / 43.1
47.5 / 43.1
47.5 / 43.1
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
24.0 / 24.0
28.2 / 24.0
28.2 / 24.0
Sump Heater Rating
W
75
130 + 75
130 + 75
Start Amps (2)
A
260 / 260
320 / 260
320 / 260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
42.8
42.8
Circuit 2 Comp RLA (PFC)
36.5
36.5
36.5
Nominal Run Amps
A
261.9
272.2
280.8
Maximum Start Amps
A
485.4
549.4
558.0
Compressor Nominal Run Amps
A
36.5 / 36.5
42.8 / 36.5
42.8 / 36.5
Recommended Mains Fuse Size
A
315
355
355
Electronic Soft-start
Nominal Run Amps
A
301.4
306.1
314.7
Maximum Start Amps
A
414.3
403.1
411.7
Recommended Mains Fuse
A
315
355
355
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
261.9
272.2
280.8
Maximum Start Amps
A
381.4
378.6
387.2
Compressor Nominal Run Amps
A
36.5 / 36.5
42.8 / 36.5
42.8 / 36.5
Recommended Mains Fuse Size
A
315
355
355
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
12
12
12
Unit Nominal Run Amps
A
313.4
318.1
326.7
Recommended Mains Fuse Size
A
355
355
355
Motor Rating
kW
5.5
5.5
5.5
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14
14
14
Unit Nominal Run Amps
A
315.4
320.1
328.7
Recommended Mains Fuse Size
A
355
355
355
Motor Rating
kW
7.5
7.5
7.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
312.6
317.3
325.9
Recommended Mains Fuse Size
A
355
355
355
Motor Rating
kW
5.5
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
14.8
14.8
Unit Nominal Run Amps
A
312.6
320.9
329.5
Recommended Mains Fuse Size
A
355
355
355
Motor Rating
kW
5.5
7.5
7.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.