Electrical Data Free Cool Chiller Extra Quiet Continued
ELECTRICAL DATA
DCF032DX-08BLM0
DCF035DX-08BMM0
Unit Data
Nominal Run Amps
(1)
A
201.1
210.0
Maximum Start Amps
A
473.6
482.5
Recommended Mains Fuse Size
A
250
250
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
External Trace Heating
Available (fitted by others)
W
500
500
Condenser Fan - Per Fan (AC)
Quantity
8
8
Full Load Amps
A
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
Motor Rating
kW
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
8
8
Full Load Amps
A
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1 / 47.5
47.5 / 47.5
Quantity
2 + 2
2 + 2
Motor Rating
kW
24.0 / 28.2
28.2 / 28.2
Sump Heater Rating
W
75 + 130
130
Start Amps
A
260 / 320
320 / 320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
42.8
Circuit 2 Comp RLA (PFC)
42.8
42.8
Nominal Run Amps
A
178.5
191.1
Maximum Start Amps
A
455.8
468.4
Compressor Nominal Run Amps
A
36.5 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
Electronic Soft-start
Nominal Run Amps
A
201.1
210.0
Maximum Start Amps
A
345.6
354.5
Recommended Mains Fuse
A
250.0
250.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
178.5
191.1
Maximum Start Amps
A
327.8
340.4
Compressor Nominal Run Amps
A
36.5 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
N/A
N/A
Full Load Amps
A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
N/A
N/A
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
12
12
Unit Nominal Run Amps
A
213.1
222.0
Recommended Mains Fuse Size
A
250
250
Motor Rating
kW
5.5
5.5
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14
14
Unit Nominal Run Amps
A
215.1
224.0
Recommended Mains Fuse Size
A
250
250
Motor Rating
kW
7.5
7.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
Unit Nominal Run Amps
A
212.3
221.2
Recommended Mains Fuse Size
A
250
250
Motor Rating
kW
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
Unit Nominal Run Amps
A
215.9
224.8
Recommended Mains Fuse Size
A
250
250
Motor Rating
kW
7.5
7.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.