Deltachill, Cooling performance ac fans, Deltachill ™ chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 26: Chillers

DELTACHILL
™
Chillers
26
Chillers
Technical Manual : 7022932_V1.9_11/2013
DeltaChill
Cooling Performance AC Fans
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC011SR-04AK00
5
117.1
28.9
111.6
31.7
106.0
34.8
100.0
38.2
6
120.9
29.0
115.3
31.8
109.5
34.9
103.3
38.3
7
124.7
29.2
119.1
32.0
113.1
35.0
106.8
38.4
8
128.7
29.3
122.9
32.1
116.8
35.1
110.3
38.5
9
132.7
29.5
126.8
32.2
120.5
35.3
113.8
38.7
10
136.8
29.7
130.7
32.4
124.3
35.4
117.5
38.8
DCC014SR-04AL00
5
148.7
38.7
142.2
42.1
134.5
45.6
126.1
49.5
6
153.5
38.9
146.7
42.2
138.8
45.7
130.2
49.6
7
158.5
39.1
151.3
42.3
143.2
45.9
134.4
49.8
8
163.5
39.2
156.1
42.5
147.7
46.0
138.7
49.9
9
168.6
39.4
160.9
42.6
152.3
46.2
143.0
50.1
10
173.8
39.6
165.7
42.8
157.0
46.3
147.4
50.2
DCC017SR-04AM00
5
174.1
45.1
165.5
48.9
156.3
53.1
146.3
57.6
6
179.6
45.3
170.7
49.2
161.2
53.3
151.0
57.9
7
185.1
45.6
176.0
49.4
166.2
53.6
155.7
58.1
8
190.8
45.8
181.4
49.7
171.3
53.8
160.5
58.4
9
196.5
46.0
186.9
49.9
176.5
54.1
165.4
58.7
10
202.3
46.3
192.4
50.2
181.8
54.4
170.4
58.9
DCC021SR-04BS00
5
215.6
58.9
204.5
63.9
192.4
69.5
179.4
75.6
6
222.2
59.2
210.8
64.3
198.4
69.8
185.0
76.0
7
229.0
59.5
217.2
64.6
204.5
70.2
190.8
76.3
8
235.8
59.8
223.7
64.9
210.7
70.5
196.6
76.7
9
242.8
60.1
230.4
65.2
217.0
70.9
202.5
77.0
10
249.8
60.5
237.1
65.6
223.3
71.2
208.5
77.4
DCC023SR-04BT00
5
248.6
70.6
234.9
76.7
220.2
83.3
204.5
90.7
6
256.1
71.1
241.9
77.2
226.8
83.9
210.7
91.2
7
263.7
71.6
249.1
77.7
233.6
84.4
217.0
91.8
8
271.3
72.1
256.4
78.3
240.4
85.0
223.4
92.3
9
279.1
72.7
263.7
78.8
247.3
85.5
229.8
92.9
10
287.0
73.2
271.2
79.4
254.4
86.1
236.4
93.5
DCC024SR-06BT00
5
260.7
68.6
247.4
74.4
233.2
80.7
217.9
87.6
6
268.8
68.9
255.1
74.8
240.5
81.1
224.8
88.0
7
277.0
69.3
263.0
75.2
248.0
81.5
231.9
88.4
8
285.4
69.6
271.0
75.5
255.6
81.9
239.0
88.8
9
294.0
70.0
279.2
75.9
263.3
82.3
246.3
89.2
10
302.6
70.4
287.4
76.3
271.1
82.7
253.6
89.7
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.