Electrical Data Free Cool Chiller Extra Quiet Continued
ELECTRICAL DATA
DCF039DX-10BMS0
DCF044DX-12BSS0
Unit Data
Nominal Run Amps
(1)
A
249.2
288.4
Maximum Start Amps
A
521.7
505.3
Recommended Mains Fuse Size
A
315
315
Mains Supply
VAC
Max Mains Incoming Cable Size
mm²
Recommended Permanent Fuse Size
A
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
External Trace Heating
Available (fitted by others)
W
500
500
Condenser Fan - Per Fan (AC)
Quantity
10
12
Full Load Amps
A
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
Motor Rating
kW
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
10
12
Full Load Amps
A
3.4
3.4
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
2.2
2.2
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 43.1
43.1 / 43.1
Quantity
2 + 3
3 + 3
Motor Rating
kW
28.2 / 24.0
24.0 / 24.0
Sump Heater Rating
W
130 + 75
75
Start Amps
A
320 / 260
260 / 260
Type Of Start
Direct on line
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
36.5
Circuit 2 Comp RLA (PFC)
36.5
36.5
Nominal Run Amps
A
220.0
248.9
Maximum Start Amps
A
497.2
472.4
Compressor Nominal Run Amps
A
42.8 / 36.5
36.5 / 36.5
Recommended Mains Fuse Size
A
315
315
Electronic Soft-start
Nominal Run Amps
A
249.2
288.4
Maximum Start Amps
A
393.7
401.3
Recommended Mains Fuse
A
315.0
315.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
220.0
248.9
Maximum Start Amps
A
369.2
368.4
Compressor Nominal Run Amps
A
42.8 / 36.5
36.5 / 36.5
Recommended Mains Fuse Size
A
315
315
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
N/A
N/A
Full Load Amps
A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
N/A
N/A
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14
14
Unit Nominal Run Amps
A
263.2
302.4
Recommended Mains Fuse Size
A
315
355
Motor Rating
kW
7.5
7.5
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
20.8
20.8
Unit Nominal Run Amps
A
270.0
309.2
Recommended Mains Fuse Size
A
315
355
Motor Rating
kW
11
11
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
Unit Nominal Run Amps
A
264.0
303.2
Recommended Mains Fuse Size
A
315
355
Motor Rating
kW
7.5
7.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
Unit Nominal Run Amps
A
270.4
309.6
Recommended Mains Fuse Size
A
315
355
Motor Rating
kW
11
11
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.