Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC036DX-08BMS0
DCC038DX-10BMS0
DCC039DX-08BSS0
Unit Data
Nominal Run Amps
(1)
A
244.2
249.2
278.4
Maximum Start Amps
(2)
A
516.7
521.7
495.3
Recommended Mains Fuse Size
A
315
315
315
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
8
10
8
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
8
10
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1 / 47.5
43.1 / 47.5
43.1 / 43.1
Quantity
3 + 2
3 + 2
3 + 3
Motor Rating
kW
24.0 / 28.2
24.0 / 28.2
24.0 / 24.0
Sump Heater Rating
W
130 + 75
130 + 75
75
Start Amps (2)
A
260 / 320
260 / 320
260 / 260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
36.5
36.5
Circuit 2 Comp RLA (PFC)
42.8
42.8
36.5
Nominal Run Amps
A
215.0
220.0
238.9
Maximum Start Amps
A
492.2
497.2
462.4
Compressor Nominal Run Amps
A
36.5 / 42.8
36.5 / 42.8
36.5 / 36.5
Recommended Mains Fuse Size
A
315
315
315
Electronic Soft-start
Nominal Run Amps
A
244.2
249.2
278.4
Maximum Start Amps
A
388.7
393.7
391.3
Recommended Mains Fuse
A
315
315
315
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
215.0
220.0
238.9
Maximum Start Amps
A
364.2
369.2
358.4
Compressor Nominal Run Amps
A
36.5 / 42.8
36.5 / 42.8
36.5 / 36.5
Recommended Mains Fuse Size
A
315
315
315
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
12
Unit Nominal Run Amps
A
253.1
258.1
290.4
Recommended Mains Fuse Size
A
315
315
315
Motor Rating
kW
4
4
5.5
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
12
12
14
Unit Nominal Run Amps
A
256.2
261.2
292.4
Recommended Mains Fuse Size
A
315
315
315
Motor Rating
kW
5.5
5.5
7.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
255.4
260.4
289.6
Recommended Mains Fuse Size
A
315
315
315
Motor Rating
kW
5.5
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
255.4
260.4
289.6
Recommended Mains Fuse Size
A
315
315
315
Motor Rating
kW
5.5
5.5
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.