Chillers deltachill, Chillers, Electrical data extra quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 79

Chillers
DELTACHILL
™
Chillers
79
Technical Manual :7022932_V1.9_11/2013
Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC019DX-04AFK0
DCC020DX-06AFK0
DCC021DX-04AKK0
Unit Data
Nominal Run Amps
(1)
A
123.5
123.5
142.1
Maximum Start Amps
(2)
A
336.0
396.0
324.1
Recommended Mains Fuse Size
A
160
160
160
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
33.0 / 47.5
33.0 / 47.5
33.0 / 33.0
Quantity
2 + 1
2 + 1
2 + 2
Motor Rating
kW
18.8 / 28.2
18.8 / 28.2
13.7 / 18.8
Sump Heater Rating
W
131 + 75
130 + 75
75
Start Amps (2)
A
215 / 260
215 / 320
215 / 215
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
28.5
28.5
28.5
Circuit 2 Comp RLA (PFC)
42.8
42.8
28.5
Nominal Run Amps
A
109.8
109.8
124.0
Maximum Start Amps
A
387.0
387.0
310.5
Compressor Nominal Run Amps
A
28.5 / 42.8
28.5 / 42.8
28.5 / 28.5
Recommended Mains Fuse Size
A
160
160
160
Electronic Soft-start
Nominal Run Amps
A
123.5
123.5
142.1
Maximum Start Amps
A
232.0
268.0
238.1
Recommended Mains Fuse
A
160
160
160
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
109.8
109.8
124.0
Maximum Start Amps
A
259.0
259.0
224.5
Compressor Nominal Run Amps
A
28.5 / 42.8
28.5 / 42.8
28.5 / 28.5
Recommended Mains Fuse Size
A
160
160
160
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
128.5
128.5
147.1
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
2.2
2.2
2.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.6
6.6
6.6
Unit Nominal Run Amps
A
130.1
130.1
148.7
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
3
3
3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
4.5
4.5
4.5
Unit Nominal Run Amps
A
128.0
128.0
146.5
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
2.2
2.2
2.2
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
6.3
Unit Nominal Run Amps
A
129.8
129.8
148.4
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
3
3
3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.