Unit lifting, Chillers deltachill, Installation data – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 151

Chillers
DELTACHILL
™
Chillers
151
Technical Manual :7022932_V1.9_11/2013
Installation Data
Unit Lifting
Employ lifting specialists
Local codes and regulations relating to the lifting of this type of equipment should
be observed
Use the appropriate spreader bars/lifting slings (provided by others) with the eye
bolts/lugs provided
Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit
Lifting eye bolt
Number of Condenser Fans
4 Fan
6 Fan
8 fan
10 fan
12 fan
Eyebolt size
M24
M30
M30
M30
M36
IMPORTANT
Do not use 1 chain between 2 lifting points to avoid load shift.
Only use lifting points provided.
Chains/slings MUST NOT interfere with the casing or fan assembly to
avoid damage.
Lift the unit slowly and evenly.
If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.
Lifting Dimensions
A
C
B
2300
A
B
C
4 Fan
mm
4000
1850
208
6 Fan
mm
4000
2186
210
8 Fan
mm
4000
3502
518
10 Fan
mm
4000
3336
1166
12 Fan
mm
5000
4745
1030