Technical data – West Control Solutions N8840 User Manual
Page 83
Technical data
8840 profiler
83
Thermoelementtype
Measuring range
Accuracy
Resolution (Ô)
L
Fe-CuNi (DIN)
-100...900°C
-148...1652°F
ß 2K
0,1 K
J
Fe-CuNi
-100...1200°C
-148...2192°F
ß 2K
0,1 K
K
NiCr-Ni
-100...1350°C
-148...2462°F
ß 2K
0,2 K
N
Nicrosil/Nisil
-100...1300°C
-148...2372°F
ß 2K
0,2 K
S
PtRh-Pt 10%
0...1760°C
32...3200°F
ß 2K
0,2 K
R
PtRh-Pt 13%
0...1760°C
32...3200°F
ß 2K
0,2 K
T
Cu-CuNi
-200...400°C
-328...752°F
ß 2K
0,05 K
C
W5%Re-W26%Re
0...2315°C
32...4199°F
ß 2K
0,4 K
D
W3%Re-W25%Re
0...2315°C
32...4199°F
ß 2K
0,4 K
E
NiCr-CuNi
-100...1000°C
-148...1832°F
ß 2K
0,1 K
B * PtRh-Pt6%
0(100)...1820°C
32(212)...3308°F ß 2K
0,3 K
* Specifications valid for 400°C
Table 1 Thermocouples measuring ranges
Type
Signal current Measuring range
Accuracy
Resolution (Ô)
Pt100
0,2mA
-200...100°C
-140...212°F
ß 1K
0,1K
Pt100
-200...850°C
-140...1562°F
ß 1K
0,1K
Pt1000
-200...850°C
-140...392°F
ß 2K
0,1K
KTY 11-6 *
-50...150°C
-58...302°F
ß 0,2K
0,01K
Spezial
0...4500
ß
0,1%
0,01 %
Spezial
0...450
Poti
0...160
Poti
0...450
Poti
0...1600
Poti
0...4500
* Or special
Table 2 Resistance transducer measuring ranges
Measuring range Input impedance
Accuracy
Resolution (Ô)
0-10 Volt
~ 110 kΩ
ß 0,1 %
0,6 mV
-2,5-115 mV
?
1MΩ
ß
0,1 %
6 µV
-25-1150 mV
?
1MΩ
ß
0,1 %
60 µV
0-20 mA
20 Ω
ß 0,1 %
1,5 µA
Table 3 Current and voltage measuring ranges