7.3.3 Operation
Programmer operation (run/stop, preset und reset) is via front panel, digital inputs
or interface (8800/8840 Configurator, superordinate visualization, ...).
Front panel operation
For programmer operation via the front panel keys, the digital input function
(di.Fn
r
page 36) must be set to key operation.
Function key
è
can be used for switch-over to programmer
or
controller
. If programmer was selected, the func LED is lit.
Now, the programmer can be started or stopped via auto/manual key
H
(run LED
= ON or OFF). By pressing auto/manual key
H
during stop condition, the
programmer jumps to the end segment. Press the key again to switch off the
programmer (reset).
Operation via digital inputs
Functions start/stop and reset can be activated also via digital inputs. For this,
parameters P.run and P.oFF must be set for digital inputs (
r
page 35, 36) at
CONF level LOGI (
r
page 35, 36).
Program/segment selection
Prerequisite: Programmer is in the reset or stop condition. How to select a
defined program (Pr.no) followed by a segment (Pr.SG) is shown below. When
starting the programmer now, program operation starts at the beginning of the
selected segment in the selected program.
Preset
The preset function is activated via segment selection.
To permit preset in a running program, switch the programmer to stop, select the
target segment as described in the above section and switch the programmer to
run.